Terminator

TM

ECM-R-XP

INSTALLATION PROCEDURES

13.

Install power cable.

15.

Use the rotary switches for settling

Control and Limit Temperature,

(Celcius or Fahrenheit) and Auto or

Manual reset (Control switches on

Type "C", Limiter switches on Type

"L" and both on Type "CL").

14.

Install electronic control module and

complete system wiring. Terminal set

screws shall be tightened to a torque

value of 1,4 Nm (12,4 lb-in). See

wiring details. Set modules electronic

control and/or control limiter at desired

setpoints.

12.

Remove M25 dust cap. Install M25

power gland (order separately) and

M25 blind plug.

11.

Mount junction box base on expediter.

Make sure to align slots to properly

orient junction box base. Tighten nut

with Terminator-LN-Tool. If mounting

horizontally, threaded gland holes must

face downward.

10.

Fix expediter, RTD, and lead wire to pipe.

16.

Install junction box lid and twist hand

tight. Insert screwdriver into ratchet slots

located on side of junction box base.

17.

Use screwdriver to ratchet on junction

box lid. Lid will rotate 30 degrees.

18.

Lid latch mechanism fully engaged. To

remove lid, repeat steps 16 and 17 but

in the opposite direction.