Mineral Insulated Heating Cable

Heating Cable

Tie Wire or

Banding (TYP.)

Illustration I: Socket Weld Valve

. . .

Notes. . .

1. For small valves (less than 2") it may be impractical to install the correct cable allow-

ance on the valve body itself. It can be installed in a uniform manner across the valve

and either side of the pipe as shown above .

2. At tee branch pipe line (less than 2") if the branch pipe is double traced and the main

pipe is single traced, then there is no additional requirement for cable allowance for

valve.

Stainless Steel Tie Wire

or Banding

MIQ Heater Cable

Illustration H: Pipe Hanger

. . .

Pipe Hanger

MIQ Heater Cable

Stainless Steel Tie Wire

or Banding

Installation on Tanks and Vessels

. . .

Always install MIQ cable longitudinally on surface of tanks or
vessels. Never spiral wrap MIQ around circumference of tanks
or vessels.