MIQ

TM

Mineral Insulated Heating Cable

MIQ Catalogue Reference Number . . .

A complete catalogue reference number will typically include the following components:

The following installation procedures are suggested guidelines
for the installation of a Thermon MIQ mineral insulated heat
tracing system. Refer to project specifications, if applicable.

Applications . . .

1. MIQ heating cables are used for freeze protection or tem-

perature maintenance of piping, tanks and instrumentation.

2. Heat tracing cables may be installed in ordinary (nonclassi-

fied) and hazardous (classified) locations depending on the
specific cable options and approvals.

Determine Heat loss. . .

There are several ways to determine the heat loss for pipes un-
der given set of design conditions:

• Heat loss calculation such as those detailed in IEEE

Std.515 (IEEE Standard for the Testing, Design, Installa-
tion, and Maintenance of Electrical Resistance Heat Tracing
for Industrial Applications).

• Computer-aided design programs that allow the user

to input detailed information specific to an application.
(Thermon's CompuTrace

®

design and selection program

provides this and more based on the formulas presented
in IEEE Std.515).

• Heat loss charts based on selected pipe diameters, tem-

perature differentials and insulation materials.

• Please contact Thermon for additional information on pipe

and vessel heat loss.

The National Electric Code and Canadian Electrical

Code require ground-fault protection be provided

for electric heat tracing.

Cold Lead

Wires

MIQ Heating

Cable

Hot-To-Cold

Fitting

Cable Set Strain

Relief Fitting

MIQ Cold

Lead

Hot End

Termination

Gland

Connector

D / MIQ-50E3H-2S / 200 / 1404 / 120 / 4 / 12 / 6 / LW / 1

Design (A,B,D,E)
Cable Reference
Length (Feet or Meters)

1

Watts
Volts
Cold Lead Length (Feet or Meters)

1

Cold Lead size (AWG)
Cold Lead Voltage Rating
Laser Welded Fitting

2

Hazardous (Classified) Location Rating

3

Notes. . .

1. The measurement in feet is standard. Metric lengths are followed by the letter “m

”.

2. If the field is blank, then the heating cable set utilizes silver braze connections.
3. If the field is blank, then the heating cable set is intended for ordinary (non-classified)

locations or D2, AEx de, or Ex de hazardous (classified) locations. If the value in the

field is “1”, then the heating cable set is intended for D1, AEx d, or Ex d hazardous

(classified) location.