Installation on Elbows, Supports and Flanges . . .

1. Install heating cable in accordance with Illustrations C thru

E below. Secure heating cable to piping using stainless
steel tie wire or banding.

2. Elbows: Locate the cable on the outside radius of an elbow

to provide sufficient heat to compensate for the added
piping material. Secure the cable to the pipe on each side
of the elbow with stainless steel tie wire or banding.

3. Pipe Supports: Insulated pipe supports require no ad-

ditional heating cable. For uninsulated supports, allow two
times the length of the pipe support plus an additional 15”
(40 cm) of heating cable.

Flange Size

IN

(mm)

1/2

(12)

3/4

(19)

1

(25)

1 1/4

(32)

1 1/2

(40)

2

(50)

3

(80)

4

(100)

6

(150)

8

(200)

10

(250)

12

(300)

14

(350)

16

(400)

18

(450)

20

(500)

24

(600)

30

(750)

Flange

Allowance

IN

(mm)

6

(150)

7

(180)

7

(180)

7

(180))

8

(205)

8

(205)

10

(255)

11

(280)

12

(305)

13

(330)

14

(356)

16

(406)

18

(457)

19

(483)

20

(508)

21

(533)

24

(610)

26

(660)

Table 1 Flange Allowance (pair) . . .

NOTE:

Slack cable can be taken up by running the cable on the outside radius of the pipe

elbows. Running the cable on the inside radius of the pipe elbows will add slack to the

cable.

MIQ

Heating Cable

3" Max.

(8 cm)

Avoid Bolts

Illustration E: Pipe Flange . . .

Stainless Steel

Tie Wire

or Banding

Illustration C: Pipe Elbow . . .

MIQ Heating Cable

Cable To Sweep Around

Outside Diameter Of Pipe

Stainless Steel

Tie Wire

or Banding

Illustration D: Pipe Support . . .

MIQ Heating Cable

NOTE:

Loop cable 3 inches past pipe shoe support on both sides.

Stainless Steel Tie Wire

or Banding

3" Min.

(8 cm)

Support

Length

3" Min.

(8 cm)

4. Flanges: Heating cable should maintain contact with flange

when bending around pipe flanges to compensate for
additional heat loss. In potentially explosive areas, it is
recommended to secure MIQ cable with stainless steel
banding at all flanges or any other irregular shaped equip-
ment.

5. Minimum bend radius is 6X cable OD. Do not exceed

bend radius when completing installation.

5