Petk, Installation procedures – Thermon PETK User Manual

Page 3

background image

3

Step 2:

Matrix Removal for BSX, RSX, HTSX, KSX, and VSX Cables

2b.

Cut a 4mm strip of conductive matrix

between the conductors.

Do not cut bus wire strands.

2c.

Cut and remove the 4mm matrix strip.

2a.

Cut and remove primary insulation jacket

(BSX and RSX cables only).

Step 1:

Remove Heating Cable Overjacket and Separate Metallic Braid to Form Pigtail

1b.

Separate braid strands at edge of over-

jacket and pull cable through opening in

braid.

1c.

Twist braid into a pigtail. Trim ends of

braid.

1a.

Cut and remove heating cable overjacket.

Do

not cut metallic braid.

For HPT and FP cable exchange grommet

supplied in Terminator kit with:

GRW-G provided in PETK-3

GRW-GT2 provided in PETK-3-ECM

GRW-G/Tstat provided in PETK-3-ZT

IMPORTANT!

Heating cable must be

properly installed within

expediter assembly and

mounted to pipe prior to

terminating with PETK kit.

See Terminator Installation

Instructions for expediter

mounting details.

152 mm

(6”)

PETK

INSTALLATION PROCEDURES

4 mm

(.15”)

4 mm

(.15”)

Terminator: Route cable through base entry

and mount expediter to pipe using pipe band.

Do not band over cable.

GRW

GRW-G

GRW-GT2

GRW-G/Tstat