2 register addresses – Tecfluid MX4B User Manual
Page 6
![background image](https://www.manualsdir.com/files/807349/content/doc006.png)
6
Holding Registers (Read write)
4.2 Register
addresses
The addresses for the different data are the following:
Input Registers (Read only)
Access (Hex)
Data
Type
0x2000
Flow rate MSB
Floating point
0x2001
Flow rate LSB
Floating point
0x2002 Reserved
---
Address (Hex)
Data
Type
0x3000
Totalizer MSB
Floating point
0x3001
Totalizer LSB
Floating point
0x3002
Flow rate 4 mA MSB
Floating point
0x3003
Flow rate 4 mA LSB
Floating point
0x3004
Flow rate 20 mA MSB
Floating point
0x3005
Flow rate 20 mA LSB
Floating point
0x3006 Totalizer
units Integer
0x3007
Flow rate units
Integer
0x3008 Filter Integer
0x3009 Status Integer
0x300A Reserved
---
0x300B Reserved
---
0x300C Reserved
---
Data Format
Type
Flow rate
Floating point IEEE 754 32 bits
Read only
Total
Floating point IEEE 754 32 bits
Read write
Analog output 4 mA value
Floating point IEEE 754 32 bits
Read write
Analog output 20 mA value
Floating point IEEE 754 32 bits
Read write
Integration filter
Integer 16 bits
Read write
Status
Integer 16 bits
Read only