14

In some cases in which several devices are connected in a line it is necessary to incorporate
an impedance at the end. If the converter MX4B is the last device of the line, the impedance
can be set by placing a jumper in the position shown in the figure below.

Terminal

1 B

2 A

13 GND

It is recommended that the shield is connected to ground only in one of its ends.

The cable connection between the MX4B converter and a Master is the following:

MX4B Converter

Master

Terminal A

A/D-

Terminal B

B/D+

GND

G/Reference