Appendix 1 – factory defaults, Universal defaults – Super Systems HP15 User Manual
Page 19

HP 15 Manual Rev A
Page 19 of 19
Appendix 1 – Factory Defaults
Universal Defaults
• Temperature in °F
• All Baud Rates initially 19200 and set for Modbus
• Burnoff time is 90 seconds
• Burnoff recovery wait time is 2 minutes
• Burnoff interval is 12 hours
• Burnoff maximum temperature is 2000 °F
• CO Factor is 200
• Hydrogen factor for Dewpoint calculation is 40%
• Analog to Digital Converter filter time is 8 seconds for all 3 ADCs
• For analog input 1 initial scale is 0, and full scale is 1000
• For analog input 2 initial scale is 0, and full scale is 10000
• For analog input 3 initial scale is 0, and full scale is 10000
• First Process Control Setpoint is set to 0
• First Process Proportional Band is 20%
• First Process Reset for PID control is On
• First Process Rate for PID control is 0
• First Process Output Cycle Time for Control is 16 milliseconds
• First Process Auto/Manual set to Automatic
• First Process Control Load Line or Manual Reset (integral preset) set to 0
• Second Process Control Setpoint is set to 0
• Second Process Proportional Band is 4.4%
• Second Process Reset for PID control is 12
• Second Process Rate for PID control is 216
• Second Process Output Cycle Time for Control is 60 milliseconds
• Second Process Auto/Manual set to Automatic
• Second Process Control Load Line or Manual Reset (integral preset) set to 0
• Start PV for temporary tuning set to 0
• Temporary Proportional band for tuning set to 2%
• Temporary reset for tuning set to On
• Temporary rate for tuning set to 0
• Temporary integral preset for tuning set to 0
• Relay 1 set for loop 2 heat
• Relay 2 set for alarm 1
• Relay 3 set for loop 1 increment (gas)
• Relay 4 set for loop 1 decrement (air)
• Relay 5 fixed by PV type.
• Relay 6 set for Probe Burnoff
• Relay 7 set for Alarm 3
• Relay 8 set for all alarms.
• Alarm 1 setpoint set for 1800
• Alarm 1 is set for analog input 2
• Alarm 1 hysteresis is set for 1
• Alarm 2 setpoint set for 2000
• Alarm 2 is set for analog input 1