Sensoray 7429 User Manual
Page 43

SET OPEN SENSOR VALUES - establish data value in event of open sensor
Channels 0-7:
command:
(80),(OPEN SENSOR FLAGS)
response:
NONE
Channels 8-15:
command:
(81),(OPEN SENSOR FLAGS)
response:
NONE
SET FILTER TIME CONSTANT - specify filter constant for a single channel
command:
(96 + CHAN),(FILTER CONSTANT)
response:
NONE
TARE GAGE - specify gage tare weight
command:
(112 + CHAN),(MSB DATA),(LSB DATA)
response:
NONE
50 HERTZ FILTER - set A/D sample interval for 50 Hz environment
command:
(128)
response:
NONE
READ ALL CHANNELS
Channels 0-7:
command:
(144)
response:
(CH0 MSB),(CH0 LSB),
(CH1 MSB),(CH1 LSB),
(CH2 MSB),(CH2 LSB),
(CH3 MSB),(CH3 LSB),
(CH4 MSB),(CH4 LSB),
(CH5 MSB),(CH5 LSB),
(CH6 MSB),(CH6 LSB),
(CH7 MSB),(CH7 LSB)
Channels 8-15:
command:
(145)
response:
(CH8 MSB),(CH8 LSB),
(CH9 MSB),(CH9 LSB),
(CH10 MSB),(CH10 LSB),
(CH11 MSB),(CH11 LSB),
(CH12 MSB),(CH12 LSB),
(CH13 MSB),(CH13 LSB),
(CH14 MSB),(CH14 LSB),
(CH15 MSB),(CH15 LSB)