Service diagnosis, Cswe1 – Scotsman CSWE1 User Manual

Page 11

background image

Service Diagnosis

Problem

Probable Cause

Possible Solution

Compressor will not run, no ice in
bin

Located in cold area

Move to warmer area (above
55

o

F.)

Power disconnected

Connect power

Defective compressor start relay

Replace relay

Service switch in OFF position

Move switch to ON

Bin thermostat contacts open

Replace bin thermostat

Defective compressor motor

Replace compressor

Control knob in Clean position

Move to ON

Compressor runs, but no ice in bin Water supply off

Restore water supply

Inlet water valve does not work

Check valve, replace if needed

Evaporator thermostat out of
calibration

Re calibrate or replace

Hot gas solenoid stuck "open"

Repair or replace

Inoperative refrigeration system

Repair sealed system

Excessive use of cubes

Advise customer

Cutter grid circuit open

Check circuit

Incorrect wiring

Check against wiring diagram

Water inlet tube from valve not
inserted into water pan

Insert tube into water pan

Compressor runs continuously,
bin full of ice

Bin thermostat out of calibration

Re calibrate or replace

Bin thermostat contacts stuck shut Replace thermostat

Incorrect wiring

Check against wiring diagram

Low ice yield

Located in cold area

Move to warmer area (above
55

o

F.)

Water falling on cubes

Check water system components
and see that they are in the
proper place

Bin thermostat out of calibration

Re calibrate or replace

Evaporator thermostat set to
produce cubes too thin or too thick

Adjust to 1/2" thick

Hot gas solenoid stuck partially
open

Replace solenoid valve

Insufficient refrigeration

Check and repair sealed system

Not enough water being
circulated over the evaporator

Check for restriction in water
lines. Check water pump and
motor.

CSWE1

December 1995

Page 11