CS55 SERVICE DIAGNOSIS

SYPMTOM............................... POSSIBLE CAUSE

SUGGESTED CORRECTION

Unit will not run........................ Blown fuse or

Replace fuse & check for

............................................ breaker

cause of blown fuse, reset breaker.

Compressor cycles .................. Low voltage

Check circuit for

intermittently ............................

overloading. Check voltage at the

............................................

supply to the building.

............................................ Dirty condenser

Clean the condenser

............................................ Air circulation

Allow sufficient air

............................................ blocked

around unit.

............................................ Non condensable

Evacuate and recharge

............................................ gas in system

with nameplate charge

Cubes too small....................... Cube size control

Check and adjust for

............................................ set too warm

proper operation

............................................ Partially restricted

Blow charge, evacuate

............................................ cap tube

with new drier, weigh in nameplate charge.

............................................ Moisture in system

Same as above

............................................ Overcharged

Same as above

............................................ Undercharged

Same as above, look for a leak.

Cloudy cubes........................... Spray nozzels

Clean

............................................ plugged
............................................ Needs cleaning

Clean with Scotsman Ice Machine Cleaner

Irregular size............................ Some jets plugged

Clean jets

cubes, some cloudy .............. Shortage of water

Check water supply

Cubes too large ....................... Cube size control

Check and adjust for

set improperly..................... proper operation

Decreased ice ......................... Inefficient

Replace

capacity.................................... compressor

December 1987

Page 13