Refrigeration

BTUH Capacity Requirements

Model

BTUH

N0622L or F0822L

4,000

N0922L, F1222L

5,000

N1322L

7,200

Condensing Units

Model

Use Condensing Unit

N0622L or F0822L

NME654-RHS-A/C

N0922L or F1222L

NME954-RHS-A/C

N1322L

None - rack only

Remote low side models require connection to
a dedicated condensing unit or a rack system.

Recommended Tubing from Head to Condensing
Unit

Suction Line: 5/8" OD

Liquid Line: 3/8" OD

Distance limits:

Maximum distance between dedicated
condensing unit and head: 75 feet.

Condensing Unit Elevation over Ice Making
Section: 35 feet.

Note: Elevations greater than 20 feet require
installation of a suction line trap at the 10 foot
mark.

Ice Making Section

Elevation over Condensing Unit: 15 feet.

Line Routing:

Allowed: One rise after a drop.

Allowed: One drop after a rise.

Not Allowed: More than one rise after a drop

Not Allowed: More than one drop after a rise

Roof Attachment

Install and attach the remote condensing unit to the
roof of the building, using the methods and
practices of construction that conform to the local
building codes, including having a roofing
contractor secure the condenser to the roof.

Refrigeration Installation:

Connections

The liquid and suction fittings on the back of the
cabinet are stubs. The liquid line size is 3/8" OD.
The suction line size is 5/8" OD.

1. Recover holding charge

2. Cut the stubs off.

3. Braze line set tubing to each fitting. Sweep with
dry nitrogen while brazing.

4. Dedicated condensing unit: Evacuate complete
system to 50 microns.

5. Open the ball valves.

Rack: The skills of a refrigeration technician are
required to connect the ice machine to the
building’s refrigeration system.

Notes:

R-404A models: 1.5 ounces of R-404A
refrigerant is in the system as a holding
charge.

Be sure the liquid connection is NOT in
series with another liquid line valve.

Local Codes must be observed.

Dedicated condensing unit: Add refrigerant charge.
Recommended starting field charge:

N0622L or F0822L: 8 lb R-404A

N0922L or F1222L: 8 lb R-404A

N1322L: n/a - rack only

July 2009

Page 8

N0622L, F0822L, N0922L, F1222L, N1322L, F1522L
Remote Low Side User's Manual