beautypg.com

RLE F200 User Manual

Page 2

background image

the Setup tab and then click on the Network link. Type the desired address into
the IP address field and click the Save Settings button.

Web Interface

Dashboard

The Dashboard is your main point of contact

for the F200. Accessible from any web

browser or mobile device, the Dashboard

display includes the status of all sensors,

digital inputs, and sensing cables connected

to and monitored by the F200.

As you connect sensors to the F200, their

information appears on the Dashboard.

If you have leak detection sensing cable

connected to the F200, you will need to use

the Inputs tab on the Setup menu to enable

the leak detection monitoring. Then it too will appear on the Dashboard. Other

items that can be configured to display on the Dashboard include digital inputs, a

button to control the relay output, and displays from IP web cameras. Configure

these items on the Sensors, Inputs, and Reporting tabs of the web interface.

Setup Menus

Use the menus in the Setup tab to configure your F200. When you begin typing

changes into any of the fields, they will turn either green to indicate your changes

are acceptable, or red, to indicate your changes cannot be submitted. If a field

turns red, you’ve likely typed more characters than the field can accept, or you’ve

entered a character that can’t be used in that field. Once you delete the excess or

offending character, the field will turn green again.

When you edit a section, a Save Settings button appears at the bottom of that

section. Click this button to save your changes. Changes will neither be saved

nor implemented until you click the Save Settings button.

Network

Use the network tab for settings including the device name, NetBios name, IP

address, primary DNS, and NTP server.

The NetBios name is used to identify resources

on a local network. The default NetBios name

is the F200’s serial number. The F200’s NetBios

name can also be used - only on a local network

- to quickly access the F200’s web interface. Edit

the NetBios name as you’d like - it must be 15

characters or less, in all capital letters. Save your

changes. Then, in the web browser’s address

bar, type rle-netbiosname/ and press enter - but

replace the netbiosname text with the actual

NetBios name of your F200. For example, the

NetBios name of the F200 is SERVERROOM, type

rle-SERVERROOM/ in the address bar. Place a

backslash after the NetBios name. This ensures the browser executes a DNS

lookup instead of a web search. Press enter to access the web interface.

You can choose to use DHCP to obtain an IP address, or to assign the F200 a static

IP. If you choose static IP, fill in the blanks with information provided by your

network administrator and remember to save your settings.

Sensors

Use the sensors tab to configure information, alarm parameters, and alarm

notification (email, audible, activate relay output, etc.) for each 1-wire sensor that is

currently connected to the F200.

Inputs

Leak Detection

The F200 monitors up to 200 feet of leak

detection cable, configured in a single

zone. If you have leak detection

cable connected to the F200 you will

need to use this menu to enable the

leak detection monitoring. Once leak

detection is enabled, the leak detection cable

icon will appear on the F200’s Dashboard.

Use the inputs tab to set the sensitivity for

the cable - if you select high sensitivity,

the F200 will alarm when it contacts a

smaller amount of water. If you select low

sensitivity, the F200 will need to come in contact with a larger amount of water

before it issues an alarm. Then establish notification parameters for a detected leak

or cable break and save your changes.

Digital Inputs

Use the inputs tab to name your digital inputs and to configure alarm and

notification parameters (email, audible, enable relay output, etc.) for each input.

Keep in mind the “When” box will tell the F200 when to send an alarm. For

instance, if your digital input is normally open, the F200 should generate an alarm

when that contact is closed. So for that input, you’d select “Closed” in the When

drop down, and then decide what notification action the F200 should take.

Network Cameras

Want to view your remote facility any time, from anywhere? Use a web camera.

Once you have one installed and running in your facility, you can link to it from the

F200. Enable the webcam capabilities and use the fields to name the camera and

direct the F200 to its streaming image. You can also enter a URL that will take

users directly to the webcam. The F200 can provide views to four cameras. Once

each camera is enabled, it will appear on the F200’s Dashboard.

Reporting

Email Notifications

Use this feature to send email alerts when the F200

goes into alarm. Enable email notifications and

enter the email addresses in the Recipients box.

Recipients will receive all email alerts generated by

the F200.

Once you save any changes made within this

section, a test email button appears. Send a test

email to ensure your notifications are working

correctly, and that your spam filter hasn’t blocked

the incoming email notifications.

Dashboard Options

Use the Reporting tab to designate English (Fahrenheit) or metric (Celsius) units.

Relay Output

When you enable the relay output, a button to control

the relay output appears on the Dashboard. The button

allows approved users to open and close the relay output

from the F200’s Dashboard. Use the options to configure

the button’s labels. Any alarm condition that is

configured to change the state of the relay output

will override the manual button control of the

relay. If an alarm is active, you cannot turn off the alarm with

the manual relay control button.

Trending and Logging

Once trending is enabled, a graph will appear on the Dashboard. To examine the

points on the graph in greater detail, use your mouse to highlight a section of the

graph and zoom into it, or use the slider bars beneath the graph to adjust the range

of the graph. Double click anywhere on the graph to return to the default view.

The sample period designates the amount of time that passes between logged data

points on the trending graph, and can be set from one second to one day. The

F200 records up to 86,400 points - a shorter sample period records more closely

grouped points for a shorter overall period of time, while a larger sample period

charts data points spaced farther apart, but over a greater overall period of time.

The trending log is downloadable as a CSV file.

Enabling event logging generates a table on the Dashboard that logs all major

alarm events with a date and time stamp, as well as the return to normal date and

time for each event.

SNMPv2 and Modbus TCP

The F200 can be configured to communicate via SNMPv2 and Modbus TCP. If you

wish to use this functionality, configure the settings on this page. Note that links in

these headings allow you to download the SNMPv2 MIB file and to view the current

readings of all the F200’s Modbus TCP registers.

A separate document, available in the Support section of RLE’s website, further

details the F200’s Modbus capabilities.

Admin

Firmware Updates

When you click the Check for Updates button, the F200 will check with RLE to see

if it needs a firmware update. If it does, it will download and install the firmware

on its own, and then reboot itself once the firmware is installed. Once the reboot

is complete, the F200 will be ready to resume its operations. Please be sure not to

access or configure the F200 while it’s downloading and installing new firmware.

System Controls

The reboot button allows users to remotely reboot the F200. Use the Identify

button to make the unit’s LED flash and its audible alarm to sound. This helps

users connect a web interface with an actual physical unit.

Users

Two types of users can be configured on the F200. Up to eight usernames can

be configured in each of the two categories. Each username can be used by only

one user at a time. It is very important for each user to have their own

username:

• Admin User - Admin Users can view and edit the F200’s Setup screens.

• Normal User - Normal (Read Only) Users can only view the F200’s Dashboard.

There are three login configurations:

• Never - Users are never required to log in. Anyone can view the Dashboard

and Setup screens, and anyone can change the F200’s configuration through

the Setup screens.

• To Change Settings - A login is NOT required to view the Dashboard. Only

users logged in as Admin Users can view and edit the Setup screens.

• Always - All users are required to log in. Normal Users can only view the

Dashboard. Admin Users can also view and edit Setup screens.

A relay control checkbox is also located on this page. If you check this checkbox,

only Admin users will be able to operate the Relay button on the Dashboard.

Logout

If you’re logged in to the F200 and have finished your configuration work, click this

link. It will log you out of the device and return the view via your workstation back

to its read-only state.