Ft m m a, Modbus registers, Front panel indicators – RLE 10K Quick Start User Manual

Page 2: Cbr 675, Sh10

background image

Modbus Registers

The SeaHawk 10K uses its EIA-485 port to communicate via Modbus. The SeaHawk 10K

is configured to act as a slave device on a common network and is a slave only device – it

will never initiate a communications sequence.

Read Input Registers

Front Panel Indicators

The front panel of the SeaHawk 10K contains a 4-character LED and series of colored

LEDs that are used together to convey device status and information regarding detected

leaks and cable faults. A blue button is used to cycle the 4-character LED, silence the

audible alarm, and reset the alarm.

Indicator

Symbol

Description

4-character

LED

System is running in its normal operating state.

A leak, fault, or contamination has been detected. A numerical distance displays on

the LED. A green LED lights next to

Ft or m, and either the LED next to the water

drop glows red to indicate a leak, or the LED next to the wrench glows yellow to

indicate cable contamination. If the distance is measured in meters, a tenths place

decimal value will appear in measurements from 0.0 - 999.9. All meter values over

1000 will display as whole meter measurements.

Cable break/fault detected. Yellow LED flashes next to wrench symbol.

LED

Red LED - leak is detected - distance is displayed on 4-character LED

Yellow LED - Cable fault - 4-characted LED displays

cbr

Yellow LED - Cable contamination - 4-character LED displays distance

Green LED - Power on

Green LED - Measurements are made in feet

Green LED - Measurements are made in meters

Green LED - Microamps of current on cable - amperage displayed on 4-character LED

Test/Reset/

Alarm Silence

Button

Blue Push

Button

In normal operating conditions, the button functions include:

Press once: Displays cable current in ohms/foot and the green LED lights next to

the microamp symbol

Press twice: Displays the length of installed cable components and the green

LED lights next to the appropriate

Ft or m symbol

Press three times: Return to the default display (SH10 )

Press and hold: Self-test is initiated and the character display reads

cal 8060,

which indicates the value of the test resistor.

If an alarm sounds, briefly press the button to turn off the audible alarm. The Status

LED remains red, and the 4-character LED continues to show the alarm condition.
In an alarm condition, whether the audible alarm is sounding or not, press and hold

this button for 3 seconds to clear the alarm.

Ft

m

m

A

cbr

675

(e.g.)

04

Input

Registers

(3x)

Description

30001

b0=Leak alarm, b1=cable break,

b2=contamination, b3=summary

30002

Leak distance

30003

0=meters, 1=feet

30004

Leakage current on cable (mA)

30005

Installed Cable Length (ft/dm)

30006

Cable resistance, leg 1 (ohms)

30007

Cable resistance, leg 2 (ohms)

30008

Resistance per foot (milliohms)

30009

Firmware version number

38001

Leak Distance - Meters (float)

38003

Cable Length - Meters (float)

Read Output Registers

03

Holding

Registers

(4x)

Description

40001

Leakage threshold (writeable)

Default 120 mA; range: 25mA-175mA

40002

Contamination threshold (writeable)

Default 50 mA; range: 25mA-175mA

40003

Re-alarm interval (read only, set with

DIP SW1)

Default: 0 (disabled); 0=disabled, 4

hours

40004

Latching alarms (read only, set with

DIP SW1)

Default: 0 (disabled); 0=disabled,

1=enabled

40005

Silence audible alarm

Default: 0 (disabled); 0=disabled,

1=enabled

40006

Reset alarm

Default: 0 (no reset); 0=do not reset,

1=reset alarm

SH10

03

Holding

Registers

(4x)

Description

40007

Sample size (writeable)

Default: 12; range 4-25; 0 sets to

default

40008

Resistance per foot in mΩ

Set to 2000-3500 or 3500-4240

40009

AC rejection mode (needed only if the

10K is AC-powered)

Default: 1 (50Hz); 0 = 60Hz, 1 = 50Hz

40010 -

40015

Not used - reads 0

40016

Leak alarm delay (writeable)

Default: 10 seconds; range: 5-999

seconds

40017

Contamination alarm delay (writeable)

Default 120 seconds; range 5-999

seconds