5

Care and maintenance

Care

Only clean the units with a damp

cloth (adding, for instance, a liquid

household cleaner).

Do not use any sharp, scouring

or solvent-based cleaners.

This ensures the operational

reliability of your equipment!

NOTE

Maintenance

We recommend concluding

a maintenance contract with

a specialist firm, which includes

annual maintenance services.

Regularly check the function of

the safety valve.


The expansion water amount at maximum
heat (approx. 80°C) represents approx.
3.5% of the tank capacity.
When the safety valve test knob is
lifted or turned to the “Test” position,
the water must flow unhindered out of
the safety valve body into the drainage
funnel.

!

ATTENTION

This can cause the cold water

supply and parts of the storage tank

connection fitting to become hot!

If the tank is not heated or when warm

water is removed, no water should be

dripping from the safety valve. If this

does occur, either the pressure in the

water pipe is greater than the permitted

value, or the safety valve is defective.

If the pressure in the water pipe is higher

than permitted, a pressure relief valve

must be used.

In hard water areas, the limescale which

forms in the tank internal boiler and

the floating deposits of limescale must

be removed by a specialist after one

to two years of operation. Cleaning is

performed through the flange opening.

1. Remove the flanged lid

2.

.

Clean the tank.

The special enamelled inner container

of the water heater must not come into

contact with scaling solvent.

Do not use an descaling pump!

3. Thoroughly flush out the unit.

4. Refit the flange, using a new seal.

tightening the bolts in a crosswise

pattern to a torque of 20 Nm.

5. Refit the flange lid.

6. Observe the heating process as per

initial operation.

The false anode which is fitted must be
checked by a specialist no longer than
every 2 years of operation (however, at
the latest when the part is removed in
steps 3/4) and this inspection must be
documented.
If servicing tasks are performed, the
cleaning and servicing flange should be
opened, and the tank inspected for any
infiltration or soiling.