Installation

The unit can be installed basically inde-
pendent of position. However, wherever
possible, the actuator should not be
installed upside down.

Slide the lever into the "Open flow"
position, so that the system can first
be flushed.

Remove the actuator with the protec-
tive cover. This will simplify installa-
tion.

Allow for approx. 25 mm of space so
the servo motor can be reinstalled.

Installation

Installation may only be performed

by authorised specialists.

NOTE

!

CAUTION

All connections must be made with
the unit in a de-energised state
(electrical system).

Do not use any boiler accessories,

soldering material or wet materi-

als of a mineral oil basis, or which

contain mineral oil, hydrocarbon or

ethylene glycol acetate.

If diluted with at least 50% water,

diethylene glycol, ethylene glycol

and propylene glycol can be used

(anti-freeze agent).

NOTE

If the flow of water is to be redirected, in-
stall the system such that the flow enters
through valve opening "AB" and exits
through valve opening "A" or "B".

In mixed systems, install the three-way
switching valve such that the water
enters through valve opening "A" or "B"
and exits through valve opening "AB".

Fit the three-way switching valve
right to the pipe itself.

During installation of the pipes, do
not grasp or hang on to

the actuator.

Steady the three-way switching valve
with your hand and tighten the pipe
connection with an open-ended
spanner or steady the valve with an
open-ended spanner and tighten the
pipe connection with an adjustable
spanner
(see diagrams on following page).