Forced-air burner and power supply

1. Check whether fuel filter is dirty.

Replace dirty filters.

2. Check that all shut-off fittings in the oil supply are

open.

3. Check that there is enough fuel in the fuel container.
4. Check whether paraffin has accumulated in the

heating oil.
This can occur even at 5 °C.

5. Check oil tubes for damage.
6. Check the sensors and capillary pipes of the safety

devices for damage or dirt.

7. Check that the temperature monitor (TW) is working

properly.

8. Check the forced-air burner for any dirt in the noz-

zle, air flow plate, filters, etc.

Unit does not start:

1. Check power supply.

400 V / 3~N.

2. Set operating switch to “I”.
3. Ensure that the “operation” lamp on the control

panel is illuminated.

It must indicate that the unit is in “heating” mode.
4. Check that the bridge circuit plug or the thermostat

plug has been plugged in correctly.

5. Check the room thermostat setting.

The temperature set on the room thermostat must
be higher than the room temperature.

6. Check whether the safety temperature limiter (STB)

was activated.
You must remove the protective cover next to the
control panel.

7. Before resetting the STB, it is absolutely necessary

to determine the reason it was activated and take
appropriate measures.
The following are possible reasons:
Unit could not cool down because the power sup-

ply was interrupted.

Temperature of air being blown out is too high be-

cause hoses are not directing air properly.

Air intakes and outlets are blocked.

8. Check whether the “burner malfunction” control

lamp on the control panel is illuminated.
If so, release the automatic burner relay by pressing
the reset button.

9. Set operating switch to “II”.

If the fan now starts running, look for the malfunc-
tion in the burner.

Troubleshooting


Prior to doing any work on the unit, unplug it from
the power supply!

Fan does not start:

1. Check whether the vane wheel is running smoothly.
2. Check whether the controller fuse in the control

panel box was activated.

3. Check whether the motor protection relay in the

control panel box was activated.

4. Check that the fan control thermostat (TR) is work-

ing properly.

Important information about resetting the burner

à If, during the start phase, the unit is switched off

again due to a malfunction, it may only be restarted
after 5 minutes have elapsed.

à Take any steps necessary to prevent another reset.

Danger of deflagration.

G

For safety purposes, repair work on the electrical
components and the burner may only be per-
formed by authorised personnel.

G

After working on the unit, conduct an electrical
safety test.

Proper Use

These units have been designed and equipped exclu-
sively to be used for heating and ventilation for industrial
and commercial purposes.
The manufacturer is not liable for any damage resulting
from non-adherence to manufacturer specifications, le-
gal requirements or any modifications to the units.

G

An operation/use other than indicated in these in-
structions is prohibited!
In the case of non-compliance, we assume no li-
ability and our guarantee becomes null and void.

Service and Guarantee


For the guarantee to be valid, the customer must com-
pletely fill out the “guarantee certificate” enclosed with
all heating units and send it back to REMKO GmbH &
Co. KG in a timely manner after purchasing of the unit
and putting it into operation.
The units have undergone several tests to ensure
proper functioning at the factory. If there are still mal-
functions that cannot be fixed by the operator using the
troubleshooting instructions, please contact your dealer
or contract partner.