Add refrigerant

The unit contains a basic quantity of refrigerant. Additional refrigerant
may be required depending on the indoor unit used.
The revised refrigerant quantities are given in the following table:

Note that the employed
refrigerant is always filled in
liquid form!

CAUTION

Commissioning

The system can be commissioned
once all the components have
been connected and tested.

A functional check should be
performed to verify its correct
function and identify any unusual
operational behaviour prior to
handing it over to the operator.

This check is dependent on the
installed indoor unit.
The procedures are specified in the
manual for the indoor unit being
commissioned.

Function test and test run

Check the following points:

Leak tightness of refrigerant
pipes.

Compressor and fan running

smoothly.

In cooling mode, cold air should

be output by the indoor unit,
and warm air should be output
by the outdoor component.

RXS 261H RXS 351H RXS 521H RXS 681H RXS 1200H

RXW 261

+ 0 g

-

-

-

-

RXW 351

-

+ 0 g

-

-

-

RXW 521

-

-

+ 0 g

-

-

RXW 681

-

-

-

+ 0 g

-

RXD 260

+ 200 g

-

-

-

-

RXD 350

-

+ 200 g

-

-

-

RXD 520

-

-

+ 200 g

-

-

RXD 680

-

-

-

+ 200 g

-

RXD 1200

-

-

-

-

+ 0 g

RXT 350

-

+ 150 g

-

-

-

RXT 520

-

-

+ 150 g

-

-

RXT 680

-

-

-

+ 150 g

-

Cooling / heating

In addition, an additional amount of refrigerant must be added for
refrigerant pipe lengths exceeding 5 meters per circuit. Refer to the
following chart:

RXS 261H RXS 351H RXS 521H RXS 681H RXS 1200H

Basic pipe length

Additional fill quantity

Up to and incl. 5 m

0 g/m

0 g/m

0 g/m

0 g/m

0 g/m

5 m to max. 25 m

25 g/m

25 g/m

25 g/m

45 g/m

65 g/m

NOTE

Check the overheating to
determine the refrigerant fill
quantity

Wear protective clothing when
handling refrigerant.

CAUTION

Commissioning should only be
performed by specially trained
personnel and documented
after the certificate has been
issued.

Observe the manuals
for the indoor unit and
outdoor component when
commissioning the entire
system.

NOTE

REMKO RXS H