Installation – REMKO RXS xxx H User Manual

Page 11

background image

Ensure a continuous and unobstructed air flow from outside,
preferably using sufficiently large air intakes.

Comply with any regulations and conditions affecting the statics of
the building. If necessary, fit acoustic installation.

Minimum clearances

The following illustration indicates

the minimum clearances for

trouble-free operation of the

equipment.

These protection zones serve to

ensure unrestricted air intake and

discharge, as well as providing

sufficient room for performing

maintenance and repairs and

preventing the unit from being
damaged.

RXS 261H

RXS 351H

RXS 521H

RXS 681H

RXS 1200H

A

100 mm

150 mm

B

700 mm

900 mm

C

400 mm

D

100 mm

150 mm

E

200 mm

400 mm

600 mm

Oil return measures

If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.

Installation

The following instructions describe

the installation of the refrigerant

circuit and the assembly Of

the indoor unit and outdoor

component.

1. The required pipe diameters are

given in the table Technical data

for the outdoor component.

2. Install the indoor unit can

connect the refrigerant pipes as

described in the manual for the

indoor unit.

3. Observe the permitted bending

radius for the refrigerant pipes

during installation. Never bend

a pipe twice in the same place.

Brittle pipes and potential

cracking are the consequences.

4. To bend the copper tubing, use

the appropriate bending tool to

prevent kinks in the tubing.

5. Lay the refrigerant pipes from

the indoor unit to the outdoor

component.

In doing so, ensure adequate

fastenings and and take

measures for the oil return!

6. Use the wall or floor brackets

to fit the outdoor component

against structural parts

approved to support the static

load.

Observe the installation

instructions for the brackets.

7. Ensure that structure-borne

sound is not transferred to parts

of the building.

Use vibration dampers to

reduce the effects of structure-

borne sound!

Minimum clearances

Air

intake

E

C

B

A

D

Air

discharge

Oil return measures

Outdoor

component

Oil pump bend

in suction pipe to

outdoor component

1 x every 2.5

metres of rising pipe

Radius:

min. 50 mm

max. 15 m

Indoor unit

Installation should only be
performed by authorised
specialists.

NOTE

11