_____________________________________________________________________ 33
PART B – INSTALLATION
Install the fireplace only as described in these instructions and using only components from the
chimney manufacturers listed in table 2.
Parts Required
•
Stratford Fireplace
•
Insulated chimney made by the manufacturers listed in table 2, with the corresponding
specifications :
−
Chimney lengths
−
Elbows (where necessary)
−
Associated components as per these installation instructions.
Additional Equipment (optional)
•
Forced Air Distribution Kit
•
Hot Air Gravity Distribution Kit
•
Fresh Air Intake Kit
•
Fire Screen
6
SAFETY INFORMATION
6.1
SUMMARY OF INSTALLATION CAUTIONS AND WARNINGS
•
THE INFORMATION GIVEN ON THE CERTIFICATION LABEL AFFIXED TO THE APPLIANCE
ALWAYS OVERRIDES THE INFORMATION PUBLISHED, IN ANY OTHER MEDIA (OWNER’S
MANUAL, CATALOGUES, FLYERS, MAGAZINES AND/OR WEB SITES).
•
MIXING OF APPLIANCE COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING
COMPONENTS MAY RESULT IN HAZARDOUS CONDTIONS. WHERE ANY SUCH CHANGES ARE
PLANNED, STOVE BUILDER INTERNATIONAL INC. SHOULD BE CONTACTED IN ADVANCE.
•
ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE
TESTING AUTHORITY VIOLATES CSA B365 (CANADA), AND ANSI NFPA 211 (USA).
•
CONNECTION BETWEEN A 2100 INSULATED CHIMNEY AND A LISTED STAINLESS STEEL
CHIMNEY LINER IS ALLOWED IF A LISTED CONNECTOR IS USED. FOLLOW INSTRUCTIONS IN
SECTION 9.9 FOR THAT KIND OF INSTALLATION.
•
IF REQUIRED, A SUPPLY OF COMBUSTION AIR SHALL BE PROVIDED TO THE ROOM.
•
DO NOT CONNECT TO OR USE IN CONJUNCTION WITH ANY AIR DISTRIBUTION DUCTWORK
UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATION.
•
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.