Supply air temperature sensor – Orion System MODGAS II User Manual
Page 8

Section 1
MODGAS II Controller
1-4
Overview and Wiring
Supply Air Temperature Sensor
The supply air temperature sensor should be located in the ductwork downstream of the unit
supply air connection. Locate the sensor in the center of the widest part of the duct. Use the
supplied template and a
5
/
16
" drill to make a hole for the sensor. Install the gasket over the probe
and mount securely to the duct using the supplied sheet metal screws. Be sure the gasket is
compressed to provide an air tight seal. For best accuracy, apply insulation on the outside of the
duct, over the sensor. This will help prevent thermal gradients from affecting the sensor.
Figure 1-3: Supply Air Sensor Installation
See also other documents in the category Orion System Hardware:
- VCM-X (88 pages)
- VCC-X Controller (120 pages)
- MUA II Controller v.2 (96 pages)
- VCM-X/RNE Controller Operator Interface SD (92 pages)
- MUA II Controller v.2 (80 pages)
- RNE Modular Controller (88 pages)
- SA E-BUS Controller (74 pages)
- OE365-15-EBA (8 pages)
- E-BUS Distribution (12 pages)
- GBD-X Controller (12 pages)
- PT-Link II N2 (72 pages)
- PT-Link II BACnet (60 pages)
- GPC-XP Controller (60 pages)
- Lag Controller (56 pages)
- OE361-13 CommLink 5 (10 pages)
- PT-Link II LON (60 pages)
- Non-Modular VAV/Zone Controller (36 pages)
- OE338-23-XX (6 pages)
- MUA II D Controller (24 pages)
- OE742-XX-VAVZ (40 pages)
- SA Controller (68 pages)
- SA Controller (70 pages)
- VCM Operator Interfaces (52 pages)
- PT-Link-LON (40 pages)
- VCM-X E-BUS Component (128 pages)
- VAV/Zone Controller (28 pages)
- VCM Controller (60 pages)
- VCM Component (96 pages)
- MHGRV-X (26 pages)
- MODGAS-XWR (28 pages)
- MODGAS-X (28 pages)
- PREHEAT-X (28 pages)
- Full Digital Module (16 pages)
- One Condenser Head Pressure Module (24 pages)
- Two Condenser Head Pressure II Module (16 pages)
- Dual Electronic Expansion Valve Module (24 pages)
- Water Source Heat Pump X2 Module (32 pages)
- Dual Digital Module (16 pages)
- Two Condenser Head Pressure Module Tulsa (24 pages)
- VCM-X/RNE Operator Interfaces (84 pages)
- Water Source Heat Pump Module (20 pages)
- Water Source Heat Pump Module Tulsa (20 pages)
- MHGRV II (12 pages)
- MHGRV III (20 pages)