Description, Mounting – Orion System OE338-23-XX User Manual
Page 2

Form: ORION-OE332-23-GPCX-Controller-01A.doc
Page
1 of 1
Description
The OE332-23-GPCX GPC-X Controller
is used for controlling equipment or
processes that cannot be controlled us-
ing a standard HVAC controller. The
Prism computer front end software is
used to interface with the GPC-X control-
ler functions. The GPC-X Controller pro-
vides the flexibility to control, schedule
and/or monitor equipment such as unit
heaters, exhaust fans, motorized lou-
vers, and other mechanical equipment.
The GPC-X has (6) configurable inputs
which will accept signals from thermistor
temperature sensors, 4-20mA or 0-
5VDC or 0-10VDC transmitters or dry
contact closures. The inputs are set for
the desired input by means of a jumper
bar. An additional modular input is pro-
vided for connection of an OE271 static
pressure sensor. The GPC-X has (5)
relay outputs for on/off control and (2)
analog outputs. With the addition of the
OE358-23-12R, 12 Relay Expansion
Module, (4) additional relay outputs (of
the 12 total relays on the module) are
available for use with the GPC-X, provid-
ing for a maximum of (9) usable relay
outputs total. The GPC-X also has (5)
separate 2 event per day schedules,
each with its own optimal start functions
built in. In addition the GPC-X provides
lead/lag start capabilities.
Mounting
The GPC-X is provided with an integral plastic enclosure which provides mounting points for mounting inside of a
control enclosure. It is recommended that the GPC-X be mounted in a control enclosure in the building equip-
ment room. An optional factory control enclosure for the GPC-X is also available.
OE332-23-GPCX
GPC-X Controller
Technical Data
OE332-23-GPCX GPC-X Controller
Power
24 Volt AC
Weight
1.5 lb.
Power Consumption
8 VA Maximum
Network Connection
RS-485
Operating Temp
10
°F to 149°F Protocol
HSI Open Protocol Token Passing
Operating Humidity
90% RH Non-Condensing
Communications
RS-485 - 9600 Baud
Inputs:
Outputs:
Type III-10kohm sensors
Total Relay Qty. On Board
5
4-20ma
0-5VDC & 0-10VDC
Total Relay Qty. Available With
Optional Expansion Board
9
Types of Allowed
Inputs
N.O. or N.C. Binary Contact
Relay Power Rating
(2 Amp @ 24 VAC)
Total Inputs Available
7
Analog Output Qty.
2
Static Pressure Inputs
1 (Modular )
Analog Output Signal
0-10 VDC
Configurable Inputs
6
Optimal Start Schedules
(5) Total - (1) for Each Schedule
Schedules Available
(5) 2 Event per day
Lead Lag Scheduling
(1) Output can be Configured
Three Year Warranty
WattMaster reserves the right to change specifications without notice