ONICON D-100 N2 User Manual
Page 17
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-N2 Network Interface Installation Guide 05/14 - 0659-4 / 18344
Page 17
************* Unidirectional Mode Meters Only *********************
* N2 READS ADF2 FOR VOLUME or MASS TOTALS.
* NOTE UNITS MULTIPLIER
CSAD “ADF2”,N,N,”VOLUMTOT”,”10GAL”
*
*Reset Volume Totals with the command Override BO ON.
CSBO “BO2”,Y,N,”RST_VOL”,”n/a”,”reset”
*
***************** End Unidirectional Mode ****************************
Sample Bidirectional Mode .ddl File
*****************************************************************
* ONICON, D-100 Display: SERIAL NUMBER XXXXXX
* PROGRAM VERSION: DM2.022
* Metasys-N2 address: XXX
* Bidirectional Mode
*
* This DDL file is device specific to the above serial number
* This data is valid at time of creation (07/20/2005 05:27:42 PM) and can be rendered invalid due
* to field programming changes to engineering units or multipliers.
*
*****************************************************************
@MODEL+
CSMODEL “ONICON”, “VND”
*
AITITLE “Analog Inputs”
BITITLE “Binary Inputs”
ADTITLE “Analog Data Points”
BOTITLE “Binary Outputs”
*
* ANALOG INPUTS COS AVAILABLE
CSAI “AI2”,N,N,”VOLUMERT”,”GPM”
*
* BINARY INPUT COS AVAILABLE
CSBI “BI1”,Y,Y, “MODEIND”, “N/A”
************* Unidirectional Mode Meters Only *********************
* N2 READS ADF2, ADF4 FOR VOLUME or MASS TOTALS.
* NOTE UNITS MULTIPLIER
CSAD “ADF2”,N,N,”M1VOLTOT”,”10GAL”
CSAD “ADF4”,N,N,”M2VOLTOT”,”10GAL”
*
*Reset Volume Totals with the command Override BO ON.
CSBO “BO2”,Y,N,”RST_VOL”,”n/a”,”reset”
*
***************** End Bidirectional Mode ****************************