ONICON D-100 N2 User Manual
Page 16
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-N2 Network Interface Installation Guide 05/14 - 0659-4 / 18344
Page 16
Energy Rate
KBTU/H
1
KBTUH
KW
1
KW
TONS
1
TONS
Volume Rate
GPM (Gal/Min)
1
GPM
L/S (L/Sec)
1
LPS
M3H (M
3
/Hr)
1
M3H
CFS (Ft
3
/Sec)
1
CFS
CFM (Ft
3
/Min)
1
CFM
None (Not defined in N2)
Any
Any
Any
2.7 AUXILIARY PULSE (Di3) TOTAL (ADF5)
D-100 LCD Display
Engineering Units
D-100 Display Multiplier
Point File Engineering Units
Description
User defined text entry
1
User defined text entry
2.6 SAMPLE .ddl FILES
Sample Unidirectional Mode .ddl File
*****************************************************************
* ONICON, D-100 Display: SERIAL NUMBER XXXXXX
* PROGRAM VERSION: DM2.022
* Metasys-N2 address: XXX
* Unidirectional Mode
*
* This DDL file is device specific to the above serial number
* This data is valid at time of creation (07/20/2005 05:27:42 PM) and can be rendered invalid due
* to field programming changes to engineering units or multipliers.
*****************************************************************
@MODEL+
CSMODEL “ONICON”, “VND”
*
AITITLE “Analog Inputs”
ADTITLE “Analog Data Points”
BOTITLE “Binary Outputs”
*
* ANALOG INPUTS COS AVAILABLE
CSAI “AI2”,N,N,”VOLUMERT”,”GPM”
*
i
IMPORTANT NOTE
Auxiliary pulse input (Di3) totalizes pulses. The engineering units and multipliers associated
with the total are not defined by the D-100; they are defined by the pulse output of the meter
connected to the auxiliary pulse input.
E.g. a domestic water meter with a pulse output is connected to the auxiliary pulse input. The
water meter output is scaled to 100 gallons per pulse. ADF5 could be configured as: CSAD
“ADF5”,N,N,”WATERTOT”,” 100GAL”