SECTION 2.0: POINT FILE (.ddl)
The D-100 Display operates in one of two operating modes, unidirectional or bidirectional flow. The
tables below contain point information for each operating mode.
The .ddl file contains the information that identifies the device to the N2 supervisory controller. It also
specifies the variables that are available to be transmitted to and from the device on the network.
The tables below contain the .ddl information.
2.1 UNIDIRECTIONAL FLOW POINT INFORMATION
Point Type
& Address
Engineering Units
Point Description
Range
AI2
Selectable (See volume/
mass rate table)
Volume or mass rate
0-999,999
AI3
User defined
Generic analog input
0-999,999
AI4
User defined
Generic analog input
0-999,999
ADF2
Selectable (See volume/
mass total table)
Volume or mass total
0-9,999,999
ADF5
User defined
Auxiliary pulse input total (Di3) 0-9,999,999
BO2
None
Reset total for ADF2
OVERRIDE Binary
Output, Object 2-ON
BO5
None
Reset total for ADF5
OVERRIDE Binary
Output, Object 5-ON
2.2 BIDIRECTIONAL FLOW POINT INFORMATION
Point Type
& Address
Engineering Units
Point Description
Range
AI2
Selectable (See volume/
mass rate table)
Volume or mass rate
0-999,999
AI3
User defined
Generic analog input
0-999,999
AI4
User defined
Generic analog input
0-999,999
ADF2
Selectable (See volume/
mass rate table)
Mode 1 volume or mass total
0-9,999,999
ADF4
Selectable (See volume/
mass rate table)
Mode 2 volume or mass total
0-9,999,999
ADF5
User defined
Auxiliary pulse input total (Di3) 0-9,999,999
BI1
None
Flow Direction Indication
0-Forward
1-Reverse
BO2
None
Reset total for ADF2
OVERRIDE Binary
Output, Object 2-ON
BO4
None
Reset total for ADF4
OVERRIDE Binary
Output, Object 2-ON
BO5
None
Reset total for ADF5
OVERRIDE Binary
Output, Object 5-ON