1.3 STANDARD FEATURES AND SPECIFICATIONS
•
Single mode Btu calculations, in either the heating or cooling mode, are totalized and
reported.
•
Two-pipe dual mode Btu calculations in both the heating mode and the cooling mode are
totalized and reported separately.
•
Auxiliary pulse input for totalizing pulse outputs from external devices such as water or
gas meters.
GENERAL SPECIFICATIONS
CALIBRATION
Flow sensor and temperature sensors are individually
calibrated, followed by a complete system calibration.
Field commissioning is also available.
ACCURACY
Differential temperature accuracy ±0.15° F over
calibrated
range
Computing non-linearity within ±0.05%
Flow sensor accuracy:
±0.5% OF READING at calibrated velocity
±1% OF READING from 3 to 30 ft/s (10:1 range)
±2% OF READING from 0.4 to 20 ft/s (50:1 range)
TEMPERATURE SENSORS
Solid state sensors are custom calibrated using N.I.S.T.
traceable temperature standards.
PROGRAMMING
Factory programmed for each specific application
MEMORY
Nonvolatile EEPROM memory retains all program parameters
and totalized values in the event of power loss.
OUTPUT SIGNALS
Isolated solid state dry contacts for mode 1 and mode
2 energy total
Contact rating: 100 mA, 50VDC maximum
Contact duration: 0.5, 1, 2 or 6 sec selectable
NETWORK INTERFACE
LonTalk
2-wire TP/FT-10F transceiver
OUTPUT SIGNALS
LONWORKS
®
Output Points: (TP/FT-10F)
Variable Description
Units
SNVT Name
Energy Total
Btu
SNVT_btu_f
Energy Rate
Watts
SNVT_power_f
Flow Rate
Liters/Sec
SNVT_flow_f
Supply Temperature
°C
SNVT_temp_f
Return Temperature
°C
SNVT_temp_f
Flow Total
Liters
SNVT_vol_f
Auxiliary Input
No Units
SNVT_count_f
BAUD RATE
78 kbps
INPUT SIGNALS
One isolated auxiliary pulse input for totalization
(Factory configurable for active pulse, open collector
sinking, open collector sourcing or dry contact pulses)
3 – 24V dc
50Hz maximum frequency
10msec minimum pulse duration
OPTIONAL LOCAL DISPLAY
Alphanumeric backlit LCD displays total energy, total, flow, energy
rate, flow rate, supply temperature and return temperature
Alpha: 16 characters, 0.2” high
Numeric: 6 digit, 0.4” high
MAINTENANCE
ONICON recommends periodic inspection and recalibration.
No other periodic maintenance is required.
TEMPERATURE RANGE
Liquid temperature range: 32° to 200°F
Ambient temperature range: 40° to 120°F
MECHANICAL
OVERALL DIMENSION:
9.25” L x 5” W x 6.5” H
TEMPERATURE THERMOWELL:
Brass thermowell (½” sweat or ¼” NPT)
ELECTRICAL
This equipment is intended for INSTALLATION
CATEGORY (OVERVOLTAGE CATEGORY) II
applications
INPUT VOLTAGE: 24 V ±10% AC 50/60 Hz or
24
V
±4
DC
INPUT CURRENT: 200 mA maximum
TERMINALS CONNECTIONS: Use 18-22 ga. Copper wire. Do
not exceed 4.5 in-lb (0.5 Nm) of torque when tightening.
WIRING:
CONDUIT: Use PVC jacketed copper cable with a wire Gauge
suitable for the length of run and required maximum current
carrying capacity. The installation must comply with all
local, state and federal codes.
PLENUM AREA: (without conduit) Use plenum rated
copper cable with a wire gauge suitable for the length of
run and required maximum current carrying capacity. The
installation must comply with all local, state and federal
building codes.
Note: Specifications are subject to change without notice.