LONWORKS TWISTED PAIR NETWORK TERMINATION

52.3 Ohm

R1

100 uf electrolytic

C1

C2

100 uf electrolytic

100 uf electrolytic

C2

C1

100 uf electrolytic

R1

105 Ohm

+

+

Connect across Lon

bus at any point.

Connect across Lon network

at each end of the bus.

+

+

LonWorks Twisted Pair Network Termination

(Recommended Cable: Belden 85102 or equiv.)

Free Topology Network (Single Termination)

Bus Network (Dual Termination)