ONICON System-30 LonWorks BTU User Manual

Page 20

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-30 BTU Measurement System LON 05/14 - 0668-2 / 18337

Page 20

FLOATING POINT OUTPUT NETWORK VARIABLES

Description

Variable Name

SNVT Name

Engineering Units

Valid Range

Flow (volume) rate

nvoVolRateLf

SNVT_flow_f

Liters/Sec

0 to 10

12

Flow (volume) total -1

nvoVol1Lf

SNVT_vol_f

Liters

0 to 10

12

Flow (volume) total -2

nvoVol2Lf

SNVT_vol_f

Liters

0 to 10

12

Supply temperature

nvoSupplyTempf

SNVT_temp_f

° C

-17.778 to 148.889

Return temperature

nvoReturnTempf

SNVT_temp_f

° C

-17.778 to 148.889

Energy rate

nvoEnrRateWf

SNVT_power_f

Watts

0 to 10

12

*Displayed energy rate

nvoDispEnrRatef

SNVT_count_f

*See note

0 to 10

12

Energy total -1

nvoBTU1f

SNVT_BTU_f

Btu

0 to 10

12

*Displayed energy total-1

nvoDispEnergy1f

SNVT_count_f

*See note

0 to 10

12

Energy total-2

nvoBTU2f

SNVT_BTU_f

Btu

0 to 10

12

*Displayed energy total-2

nvoDispEnergy2f

SNVT_count_f

*See note

0 to 10

12

Auxiliary pulse input (Di3) nvoAuxIn1

SNVT_count_f

None

0 to 10

12

* These network variables transmit energy rate and total data exactly as it is displayed on the

optional System-30 front panel display (If ordered). The value transmitted will not include any

multiplier associated with displayed total.

The ASCII character status output network variables are described in the table below.

Column 1 contains a brief description of the network variables. Column 2 contains the

network variable names. Column 3 contains the Lon SNVT used for each variable.

Column 4 contains the ASCII single characters that may be transmitted by the meter

along with a description of what they indicate.

ASCII STATUS OUTPUT NETWORK VARIABLES

Description

Variable Name

SNVT Name

Valid ASCII Characters*

Meter operating
mode indicator

nvoMeterMode

SNVT_char_ascii

S = Single mode (83)
D = Dual mode (68)
B = Bidirectional mode (66)

Mode status
indicator

nvoModeStatus SNVT_char_ascii

N = Communication lost (78)
Z = Communication restored waiting for
update (90)
H = Heating mode (mode 1) (72)
C = Cooling mode (mode 2) (67)

* Systems that are not set to decode ASCII characters will display the decimal equivalent.

These values are shown in parentheses.

4.6.2 Integer Format Output Network Variables

ONICON provides rate and total data to the network in integer format for systems that

cannot accept the floating point data. Refer to Appendices A-8 and A-9 for information on

the use of integer format SNVTs.