USING THE DISPLAY

1.1 DISPLAY AND KEYPAD

The display contains two lines of alphanumeric characters. The first line displays the current

value. The second line contains the engineering units and a multiplier which can range from

1 to 1,000,000. The multiplier is the value the number on the top line must be multiplied by to

achieve the correct value.

Three membrane keys are provided to operate the display

and program the meter.

When operating in the run mode, the SCROLL button

advances the display from one page to the next. A total

of up to 11 different pages may be available for display

depending whether the meter is operating in the single or

dual mode.

The RESET button (if enabled) allows totals to be reset to

zero. The PROGRAM button is not active when operating

in the run mode.

1.2 PROCESSOR START-UP

When power is applied to the Btu meter alphanumeric characters appear on the two lines of the

display indicating the meter is operating. Press and release the SCROLL button on the front

panel. Observe the display cycle to the next display page.

Select the SUPPLY TEMP Page. Note the displayed temperature. Confirm that it is in the expected

range. Now select the RETURN TEMP page. Again note the displayed temperature. Confirm that

it is also in the correct range.

Select the FLOW RATE page. Note the displayed flow rate. Confirm that the flow rate value is in

the correct range.

Successively pressing the SCROLL button will cycle the display through the run mode pages

summarized in the tables on the next page.

Single Mode Operation

SINGLE MODE BTU METERS – RUN MODE DISPLAY PAGES

PAGE No.

DISPLAY NAME

SELECTABLE UNITS

1

ENERGY TOTAL

BTU, TONHR or KWHR

2

FLOW TOTAL

GAL, LITER, METERS

3

3

ENERGY RATE

BTU/HR, TONS, KW

4

FLOW RATE

GPM, GPH, MGD, L/SEC, L/MIN, L/HR, METERS

3

/HR

5

INTRN TEMPERATURE

DEG F, DEG C

6

EXTRN TEMPERATURE

DEG F, DEG C

7

Di3 PULSE TOTAL

COUNTS or TEXT ENTRY

8

ALARM STATUS

NOT APPLICABLE

9

SERIAL NUMBER

NOT APPLICABLE