SECTION 4.0: DIAGNOSTICS AND COMMISSIONING
4.1 DIAGNOSTICS
The ONICON System-30 BTU MEASUREMENT SYSTEM
uses a microprocessor to calculate energy. Factory
programmed settings provide energy total outputs in
accordance with the customer’s application data. An
optional isolated analog output for energy rate, flow
rate or delta-T may also be available. Refer to the BTU
meter calibration sheet for a complete listing of factory
settings. These settings cannot be changed in the field.
Contact ONICON if changes to the calibration are required.
The System-30 is equipped with diagnostic indicator
lights that confirm the operation of the microprocessor and
its input circuitry.
Please contact ONICON if either of the diagnostic lights
indicate a potential problem with the operation of the BTU
measurement system.
4.1.1 Diagnostic Lights
Energy
Located on the end of main unit opposite the cable connection is a red LED labeled BTU.
This LED will flash as energy is transferred.
Liquid Flow
Located on the end of main unit opposite the cable connection is a red LED labeled FLOW.
This LED will flash at a rate that is proportional to the liquid flow rate. An unlit LED
indicates no flow signal.
INTEGRATED BTU METER
CERTIFICATE OF CALIBRATION
METER INFORMATION
Meter Tag:
BTU Meter Model: SYSTEM-30
Serial No: 134036
SPECIFIED INSTALLATION & OPERATING PARAMETERS
Pipe Information: 1 Inch Copper Tube
Design Maximum Flow Rate: 40.0 GPM
Design Supply Temperature: MODE 1: 45°F
Design Return Temperature: MODE 1: 55°F
Fluid: 25% Ethylene Glycol
Fluid Specific Heat: 0.885 BTU/lb°F
Fluid Density:
65.06 lb/ft³
CONFIGURATION DATA
Enclosure Type:
Input Supply Voltage: 24 AC/DC
Thermowell Type:
CALIBRATION AND PROGRAMMING DATA
Firmware Version:
CFM4.6S30
Communications Protocol:
Device Network Address:
Flow Sensor MF Code: 547.500
Programmed Units & Multipliers:
Energy Total: BTU x 1K
Energy Rate: BTU/HR x 1K
Flow Total: GAL x 10
Flow Rate: GPM x 1
Temperature: °F
Damping: 5
Pulse Duration: 500 ms
Supply Temperature Slope: 9.969
Offset: -0.870
Return Temperature Slope: 10.004
Offset: -0.130
OUTPUT SIGNAL SCALING
Energy Total(s): 1 Pulse = BTU x 1K
Flow Rate:
NA
Energy Rate: NA
Supply T:
NA
Return T:
NA
Delta T:
NA
Calibrated By:
Date:
09/01/2004
1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699
ONICON Incorporated certifies that the flow and temperature sensors provided with this Btu meter have been individually calibrated based on the
application specific data provided above; using standards directly traceable to the U.S. National Institute of Standards and
Technology (N.I.S.T.).
Shane Hamilton