SECTION 4.0: DIAGNOSTICS AND COMMISSIONING

4.1 DIAGNOSTICS

The ONICON System-30 BTU MEASUREMENT SYSTEM
uses a microprocessor to calculate energy. Factory
programmed settings provide energy total outputs in
accordance with the customer’s application data. An
optional isolated analog output for energy rate, flow
rate or delta-T may also be available. Refer to the BTU
meter calibration sheet for a complete listing of factory
settings. These settings cannot be changed in the field.
Contact ONICON if changes to the calibration are required.

The System-30 is equipped with diagnostic indicator
lights that confirm the operation of the microprocessor and
its input circuitry.

Please contact ONICON if either of the diagnostic lights
indicate a potential problem with the operation of the BTU
measurement system.

4.1.1 Diagnostic Lights

Energy

Located on the end of main unit opposite the cable connection is a red LED labeled BTU.
This LED will flash as energy is transferred.

Liquid Flow

Located on the end of main unit opposite the cable connection is a red LED labeled FLOW.
This LED will flash at a rate that is proportional to the liquid flow rate. An unlit LED
indicates no flow signal.

INTEGRATED BTU METER

CERTIFICATE OF CALIBRATION

METER INFORMATION

Meter Tag:

BTU Meter Model: SYSTEM-30

Serial No: 134036

SPECIFIED INSTALLATION & OPERATING PARAMETERS

Pipe Information: 1 Inch Copper Tube

Design Maximum Flow Rate: 40.0 GPM

Design Supply Temperature: MODE 1: 45°F

Design Return Temperature: MODE 1: 55°F

Fluid: 25% Ethylene Glycol

Fluid Specific Heat: 0.885 BTU/lb°F

Fluid Density:

65.06 lb/ft³

CONFIGURATION DATA

Enclosure Type:

Input Supply Voltage: 24 AC/DC

Thermowell Type:

CALIBRATION AND PROGRAMMING DATA

Firmware Version:

CFM4.6S30

Communications Protocol:

Device Network Address:

Flow Sensor MF Code: 547.500

Programmed Units & Multipliers:

Energy Total: BTU x 1K

Energy Rate: BTU/HR x 1K

Flow Total: GAL x 10

Flow Rate: GPM x 1

Temperature: °F

Damping: 5

Pulse Duration: 500 ms

Supply Temperature Slope: 9.969

Offset: -0.870

Return Temperature Slope: 10.004

Offset: -0.130

OUTPUT SIGNAL SCALING

Energy Total(s): 1 Pulse = BTU x 1K

Flow Rate:

NA

Energy Rate: NA

Supply T:

NA

Return T:

NA

Delta T:

NA

Calibrated By:

Date:

09/01/2004

1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699

ONICON Incorporated certifies that the flow and temperature sensors provided with this Btu meter have been individually calibrated based on the
application specific data provided above; using standards directly traceable to the U.S. National Institute of Standards and

Technology (N.I.S.T.).