beautypg.com

Caution – ONICON System-10 BTU User Manual

Page 24

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

System-10 BTU Meter Manual 03/15 - 0651-16 / 18323

Page

24

3.3.5 Isolated Analog Output(s) (Optional):

The System-10 can be configured to provide up to four isolated analog outputs of the

following five parameters: supply temperature, return temperature, flow rate, Btu rate and

delta temperature. The output type, 4-20 mA, 0-10 VDC or 5 VDC is field configurable. The

selected outputs and associated scaling are configured at the factory. See the certificate of

calibration or label located on the inside cover for analog output configuration information.

Please note: If System-10 is ordered with a flow meter capable of producing an analog

output, the output signal will be available at terminal T5.

J1

5

G

60HZ

1

J2-1

+1

5

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

1/4 AMP

TB1

D4

D3

H1

1

L1 N

Not Used

!

CAUTION

Analog outputs are all configured as active outputs. Do not apply power to any of the 4-20mA,

0-10 or 0-5 volt outputs. Doing so will damage the output.