ONICON System-10 BACnet User Manual
Page 6
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-BAC Network Interface Installation Guide 04/14 - 0652-8 / 16957
Page 6
1.4 NETWORK SIGNAL CONNECTIONS
1.4.1 BACnet MS/TP
BACnet MS/TP, 2-wire (half-duplex) serial output connections are connected to terminal
T1 as shown. Do not exceed 4.4 in-lb (0.5 Nm) of torque when tightening.
CAUTION
Only qualified service personnel should make connections between the System-10 BTU Meter
and the user’s external equipment. ONICON assumes no responsibility for damage caused to
the external equipment as a result of an improper installation.
!
Terminal
T1
Do not connect
shields to this
terminal.
CAUTION
Incoming and outgoing RS485 cable shield wires should be connected together, but must not be
connected to the Btu meter.
!