2.2 BAC OBJECTS
The System-10 BTU Meter operates in one of three operating modes: single, dual or bi-directional.
The table on the next page contains point information for each of the operating modes.
In single mode operation, only one register accumulates energy and one register accumulates
volume. Thus, only two AV points and two BV reset points are necessary.
BACNET OBJECT
OBJECT DESCRIPTION
UNITS
NOTES
Analog Input 1
Energy Rate
Btu/Hr, kW or Tons
Analog Input 2
Volume Rate
L/Sec, L/Min, L/Hr,
M
3
/Hr, GPM, CFS or
CFM
Analog Input 3
Supply Temperature
Degrees C or F
Analog Input 4
Return Temperature
Degrees C or F
Analog Value 1
Mode 1 Energy Total
Btu, TonHrs or kWHrs
Analog Value 2
Mode 1 Volume Total
Liters, M
3
, Gallons or Ft
3
Analog Value 3
Mode 2 Energy Total
Btu, TonHrs or kWHrs
Only used in dual-mode
applications.
Analog Value 4
Mode 2 Volume Total
Liters, M
3
or Gallons
Only used in dual-mode
applications.
Analog Value 5
Auxiliary Input Total
(Di3)
None
BACnet will not report
engineering units for this
object.
Analog Value 6
Operating Mode
(Single, Dual or
Bi-directional)
Not Applicable
None = 0
Single = 1
Dual = 2
BiDir = 3
Analog Value 12
Mode 1 Mode 2
Indication
Not Applicable
Mode 1 = 1
Mode 2 = 2
Binary Value 11
Zero Mode 1 Energy
Total
Not Applicable
Changing this property
from the (0) inactive state
to the (1) active state will
reset the total to zero.
(Must be priority 8 manu-
al operator).
Binary Value 12
Zero Mode 1 Volume
Total
Not Applicable
Binary Value 13
Zero Mode 2 Energy
Total
Not Applicable
Binary Value 14
Zero Mode 2 Volume
Total
Not Applicable
Binary Value 15
Zero Auxiliary Input
Total
Not Applicable