beautypg.com

ONICON System-10 BACnet User Manual

Page 11

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-BAC Network Interface Installation Guide 04/14 - 0652-8 / 16957

Page 11

1.5 BACnet MS/TP BAUD RATE, BIASING & TERMINATION

1.5.1 Baud Rate

Every ONICON Btu meter is individually programmed at the factory with application

specific data provided by the customer during the process of ordering the meter, and this

normally includes the Baud rate setting. If the Baud rate was provided, the meter will be

configured to operate at the specified rate. The standard Baud rate settings are 9600,

19200, 38400 and 76800 Baud.

If the Baud rate setting was not provided to ONICON, the System-10 will be configured to

“auto” detect the Baud rate of the network. In this configuration, the meter should detect

and automatically adjust to the proper rate when it is connected to the network.

The Baud rate setting can be manually changed in the field. The photos and table below

show the Baud rate dipswitch settings.

B1

B2

B3

B4

Rate

0

0

0

0

Autobaud

1

0

0

0

9600

0

1

0

0

19200

0

0

1

0

38400

0

0

0

1

76800

Baud Rate Dip Switches

ON

(Circuit board shown upside down for clarity.)