beautypg.com

ONICON F-3100 Series User Manual

Page 14

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3100 Flow Meter Manual 06/14 - 0670-7

Page

14

3.1.4 Minimum Straight Run Requirements

The straight run requirements presented below represent the minimum requirements
for accurate flow measurement. For optimum performance, provide as much additional
straight run as possible.

IMPORTANT NOTE

For proper operation, install the flow meter in a straight run of pipe free of bends, tees, valves,

transitions and obstructions for a distance of at least 3 diameters upstream and 2 diameters

downstream.

i

Recommended Installation

3 DIA

2 DIA

3 DIA

2 DIA

3 DIA

2 DIA

Place flow meter at least 3

pipe diameters upstream

and 2 pipe diameters

downstream from bends

and obstrutions.

Avoid downward flow

which can lead to partially

filled pipes.

The electrodes should

be located in the

horizontal axis (3 o’clock

and 9 o’clock) in order to

prevent sediment from

settling on them.

Avoid these installations

Electrode Location