ONICON F-3200 Series User Manual
Page 35
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3200 Flow Meter Manual 05/14 - 0671-12 / 18325
Page 35
4.7 ALARM MESSAGES AND ACTION TO TAKE
The F-3200 advanced transmitter is equipped with a backlit graphic LCD capable of displaying
alphanumeric and graphical data. It is also capable of displaying alarm and error messages. Three
pushbutton keys located on the membrane panel immediately below the display are used to view
the displayed data and access program functions.
Alarm Messages & Action to Take
Messages
Description
Action to Take
No Alarms
Meter functioning normally
None
Max Alarm
Threshold setting for maximum
flow alarm. Set as a percentage of
the full scale flow from 0-125%.
Check to see if the threshold is
set high enough. Re-confirm the
design maximum flow rate.
Min Alarm
Threshold setting for minimum
flow alarm. Set as a percentage of
the full scale flow from 0 – 125%
Check to see if the threshold is
set correctly. Re-confirm the
design minimum flow rate.
Flow Rate > FS
Flow rate exceeds the maximum
full scale value.
Re-confirm the design maximum
flow rate and the full scale flow
rate setting.
Pulse / Freq > FS
Pulse rate or frequency output
exceeds the maximum rate.
Re-confirm the design maximum
flow rate and the full scale pulse
rate of frequency setting.
Empty Pipe
The pipe is empty or the empty
pipe detector needs calibration.
Calibrate the empty pipe detector.
Batch Alarm
Contact ONICON
Contact ONICON
Input Noisy
Excessive noise detected at the
sensor electrodes or the remote
cable has an open connection.
Re-check all earth ground
connections and check for open
signal cable connections.
Excitation Fail
The coils or the connecting cables
are open.
Check all cable connections.
Contact ONICON.
Curr. Loop Open
The 4- 20 mA output is not
connected properly or there is
a load resistance of greater than
1000 ohms.
Re-check wiring connections.
Measure input resistance and
confirm it is less than 1000 ohms.
P. Supply Fail
Power supply is different from
that indicated on the label.
Verify that the correct voltages
are supplied to the meter.