beautypg.com

ONICON F-1100 Series User Manual

Page 43

background image

11451 Belcher Road South, Largo FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
Turbine Flow Meter Manual 05/14 - 0721-3 / 13518

Page B-4

11451 South Belcher Road, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699

www.onicon.com • [email protected]

04-14

0880-1 / 20083

Installation Hardware Instructions
Standard Installation Kit For Copper Tube
(Components Comply with NSF61)

For F-1100, F-1200 & FB-1200 Series Insertion Turbine Flow Meters

This kit must be installed prior to filling the system, or into a section of pipe that is isolated from

pressure and flow. Once installed, this kit allows for insertion and removal of the flow meter without

a system shutdown.

For Use With Kits: INSTL3 (>1”) INSTL4 & INSTL9

Directions:

1. Identify an appropriate location for the flow meter

(see pages 2-4).

2. Solder or braze the copper tee and adapter

provided.

3. Install the ball valve as shown below. Use a

paste type thread sealant. DO NOT use Teflon

®

tape.

4. Flush and fill the system prior to installing

the meter.

NOTE: Before installing the flow meter, read the entire

installation manual.

Important Note

ONICON insertion flow meters

are precision measuring devices

that must be installed according to

the instructions contained in this

document in order to maintain their

accuracy and reliability. Failure to

follow these instructions will result

in erratic operation and reduced

accuracy.

INSTALLATION KIT COMPONENTS

1” OUTLET

1” STREET

1” FULL PORT

COPPER TEE

ADAPTER

BALL VALVE

(see Sections 3.1 and 3.2).

This manual is related to the following products: