3.4 INSTALLING THE INSERTION METER

Begin by calculating the effort that will be required to hold the meter. Establish adequate footing for
this task, taking extra caution when working from a ladder or platform. Use the following formula:

E=0.11xP

Where:

E = effort in pounds

P = system pressure in pounds per square inch

Example: In a 300 PSI system, 33 pounds of effort is required to insert the meter into the pipe.

Installing the meter with a factory supplied depth gage:

After fitting the necessary plumbing hardware, flush the
entire system so that it is free of flux, solder and slag.
Prepare to install the flow meter by loosening the clamping
nut and withdrawing the turbine assembly fully into the
hot tap adapter. Next, thread the adapter on to the ball
valve using a paste type thread sealant. Do not use Teflon
tape as torn strands of the tape may wind around the
turbine, slowing down or even stopping the turbine.

Check the installation for leaks by slightly opening the
ball valve. An ‘O’ ring in the adapter seals the meter
stem against leakage. If there are any leaks around the
clamping nut or stem, DO NOT ATTEMPT TO STOP THE
LEAKAGE BY OVERTIGHTENING THE CLAMPING
NUT. Damage to this nut or the clamping ring under the
nut may prevent the assembly from properly holding
the meter in the pipe.
The clamping nut is not part of the
sealing mechanism. Any leaks in this area indicate that the
‘O’ ring is not sealing properly and you must contact the
factory for assistance.

WARNING

When you are ready to refill the system, make sure that all lines are filled with water before inserting

the turbine assembly into the stream. If the lines are not filled, air may interrupt the flowing stream

and damage the turbine assembly. A greater danger is that if this is a hot water system, some water

may flash into steam and exceed the high temperature limit for the turbine and its mechanical

assembly. This flash over could exceed the pressure ratings of the meter and the assembly could fail

allowing steam and hot water to escape causing serious injury.

!

WARNING

SYSTEM MAY BE UNDER HIGH PRESSURE. When installing the meter, adjusting its position

or removing the meter, be sure to hold the electronics enclosure firmly by hand before SLOWLY

loosening the positioning clamping nut. Failure to do this will allow the pressure to suddenly and

rapidly force the meter from the pipe causing serious injury. The meter could also be damaged or

break apart causing a break in the water seal with the resultant loss of large amounts of water. The

hand effort required to hold the meter will be 0.11 times the pipe pressure.

!