Nortec MLP RO pump station User Manual
Page 11
TI071GB-02 /06.11.09/LJ 11/12
In the F7 range - Setting parameters for the humidity regulators
Indication in display
Explanation
Range
Standard
1*PRO xx - PER xx.x
PRO - Proportional belt for humidity
regulation of the section
PER -The period (a pulse & and a
pause) in the section indicated in
seconds.
0-50
10-1000
20
60,0
1*MON xx.x -PAU xx.x
MON - The lowest pulse time during
which can be humidfied in the section.
(If the calculated time is less, the time
is added to the calculation for the next
period). Time is indicated in seconds.
PAU -The time of the forced pause
that minimum is held in each period.
The time is indicated in seconds.
0-50,0
1-200,0
5,0
10,0
1*FLU xx.x - FLOW xx
FLU -The minimum time during
which the section humidifies to ensure
exchange of water in the hoses. The
operation time is set in minutes per 30
minutes.
FLOW - The capacity in the section -
in liter per hour
0-2,0
0-1000
0,2
50
2*PRO xx - PER xx.x
PRO - Proportional belt for humidity
regulation of the section
PER -The period (a pulse & and a
pause) in the section indicated in
seconds.
0-50
10-1000
20
60,0
2*MON xx.x -PAU xx.x
MON- The lowest pulse time during
which can be humidfied in the section.
(If the calculated time is less, the time
is added to the calculation for the next
period). Time is indicated in seconds.
PAU -The time of the forced pause
that minimum is held in each period.
The time is indicated in seconds.
0-50,0
1-200,0
5,0
10,0
2*FLU xx.x - FLOW xx
FLU -The minimum time during
which the section humidifies to ensure
exchange of water in the hoses. The
operation time is set in minutes per 30
minutes.
FLOW - The capacity in the section -
in liter per hour
0-2,0
0-1000
0,2
50
3*PRO xx - PER xx.x
PRO - Proportional belt for humidity
regulation of the section
PER -The period (a pulse & and a
pause) in the section indicated in
seconds.
0-50
10-1000
20
60,0
3*MON xx.x -PAU xx.x
MON- The lowest pulse time during
which can be humidfied in the section.
(If the calculated time is less, the time
is added to the calculation for the next
period). Time is indicated in seconds.
PAU -The time of the forced pause
that minimum is held in each period.
The time is indicated in seconds.
0-50,0
1-200,0
5,0
10,0