beautypg.com

Nortec MLP RO pump station User Manual

Page 10

background image




TI071GB-02 /06.11.09/LJ 10/12

In the F6 range - Common parameters

Indication in display

Explanation

Range

Standard

MAX.SP xx %RH

The maximum limit for adjustment of
the set points.

40-90

60

INTEGRATION xx MIN

Time indication before the integration
regulation is 100%

0-100

25

PRESSOSTAT x.x SEC

Time delay of missing water pressure

0-10,0

20,0

FAN.CONTR. xx 0/2
(OPTION)

Choice of function for the fan control
of the humidifying modules.
(0) No fan automatic
(1) Automatic control
(2) The fans are operating constantly

0-2

0,0

MAX.HYG.AUT 0/1 xxxx

Choice of reset function for Max
Hygrostat security.
(0) Manual reset
(1) Automatic reset - however max.
once an hour.

0-1

0

MLPRO > 500
TEMP LIMIT1 xxxx °C

The limit value for step 1 of the
temperature protection. The system
will start producing fresh RO-water if
this limit is exceeded. This function
only runs once every 12 hours.

10-60

30

MLPRO > 500
TEMP LIMIT2 xxxx °C

The limit value for step 2 of the
temperature protection. The bypass
valve of the pump will open and flush
the water if this limit is exceeded.

10-60

40

MLPRO > 500
TEMP LIMIT3 xxxx °C

The limit value for step 3 of the
temperature protection. The pump will
stop if this limit is exceeded and will
not start before the system has cooled
down and is re-started.

10-60

50

AUT.HYG.TIME xx.x SEC

Settting the security time for
automatic reset of Max Hygrostat-
circuit.

0-10,0

1,0

RV.MIX.MODE 0/1 xxxx
(OPTION)

Choice of active raw water mixer
(0) Not active
(1) active

0-1

0,0

Bypass < xx l/t
(OPTION)

Setting the opening level of the
bypass fan

0-1000

60,0