Nortec MLP RO pump station User Manual
Page 10
TI071GB-02 /06.11.09/LJ 10/12
In the F6 range - Common parameters
Indication in display
Explanation
Range
Standard
MAX.SP xx %RH
The maximum limit for adjustment of
the set points.
40-90
60
INTEGRATION xx MIN
Time indication before the integration
regulation is 100%
0-100
25
PRESSOSTAT x.x SEC
Time delay of missing water pressure
0-10,0
20,0
FAN.CONTR. xx 0/2
(OPTION)
Choice of function for the fan control
of the humidifying modules.
(0) No fan automatic
(1) Automatic control
(2) The fans are operating constantly
0-2
0,0
MAX.HYG.AUT 0/1 xxxx
Choice of reset function for Max
Hygrostat security.
(0) Manual reset
(1) Automatic reset - however max.
once an hour.
0-1
0
MLPRO > 500
TEMP LIMIT1 xxxx °C
The limit value for step 1 of the
temperature protection. The system
will start producing fresh RO-water if
this limit is exceeded. This function
only runs once every 12 hours.
10-60
30
MLPRO > 500
TEMP LIMIT2 xxxx °C
The limit value for step 2 of the
temperature protection. The bypass
valve of the pump will open and flush
the water if this limit is exceeded.
10-60
40
MLPRO > 500
TEMP LIMIT3 xxxx °C
The limit value for step 3 of the
temperature protection. The pump will
stop if this limit is exceeded and will
not start before the system has cooled
down and is re-started.
10-60
50
AUT.HYG.TIME xx.x SEC
Settting the security time for
automatic reset of Max Hygrostat-
circuit.
0-10,0
1,0
RV.MIX.MODE 0/1 xxxx
(OPTION)
Choice of active raw water mixer
(0) Not active
(1) active
0-1
0,0
Bypass < xx l/t
(OPTION)
Setting the opening level of the
bypass fan
0-1000
60,0