8 product specifications, 1 technical data, Product specifications – Nortec ME Direct Feed User Manual
Page 36: Technical data, 8product specifications
36 Product specifications
8
Product specifications
8.1
Technical data
Nortec ME Direct Feed
With optional
On/Off control unit
With optional
Stage control unit
Supply voltage optional On/Off and stage control unit
100...240 VAC/50...60 Hz
Power consumption
1)
40 W
100 W
Control signals
On/Off
0..10 VDC
2...10 VDC
Control accuracy
Control accuracy depends on air conditions, control
distance, water quality and on the number of On/Off
cycles
Max. admissible matrix face velocity
3.5 m/s (689 fpm)
(4.5 m/s (886 fpm) with droplet separator)
Water supply
ø15mm (0.625") push-fit connector
Water drain (outside diameter)
ø 54 mm (2.125")
Admissible water supply pressure
2...5 bar (29...72.5 psi)
Admissible water temperature
5...20 °C (41...68 °F)
Water quality
Tap water, softened or fully demineralised water with a
max. of 100 cfu/ml
Admissible operating air temperature
10...60 °C (50...140 °F)
Admissible ambient temperature (optional control unit)
1...40 °C (33.8...104 °F)
Admissible ambient humidity (optional control unit)
max. 75 %rh
Degree of protection of optional control unit
IP21
Degree of protection of optional valves
IP54
Conformity
CE marking
Fire classification of evaporative media
glass fibre media: A2-S2,-D0 (UL Class 1)
polyester media: DIN EN 53438 Class F1
1)
Power consumption depending on the number of vertical evaporative cassettes banks and the options fitted