Maintenance
Operations
Minor
Service
Complete
System Service
Lightly brush evaporator cassettes if necessary, replace if heavily soiled
–––
Yes
Remove evaporator cassettes and clean all sections of tank and frame
structure
–––
Yes
Check and secure frame structure and seal
–––
Yes
Check all media for full saturation
Yes
Yes
Measure flow rates to distribution headers
–––
Yes
Check and secure all electrical connections
Yes
Yes
Check overall installation for leaks and damage
Yes
Yes
Check any options as per relevant documentation
Yes
Yes
Complete disinfection as described in this manual
Yes
Yes
Check safety interlock and humidity/temperature control devices (if ap-
plicable)
–––
Yes
Check air velocity at face of evaporative cassettes matrix
–––
Yes
Update service log book
Yes