3 product overview, 1 model overview, Product overview – Nortec ME Direct Feed User Manual
Page 10: Model overview, 3product overview
10 Product Overview
3
Product Overview
3.1
Model overview
The
standard version includes the evaporative module (75%, 85 % or 95 % efficiency depending
on the cassette type) and a
hydraulic manifold without valves (for internal or external installation).
To run the standard version with a
On/Off control, the system must be equipped with an On/Off control
unit and the hydraulic manifold must be equipped with a drain valve, a supply valve, and a purge valve
as minimum. All components for extending the standard version to an On/Off control system are avail-
able as options (see table below) or must be supplied by the customer.
To run the standard version with a
stage control, the system must be equipped with a stage control unit
and the hydraulic manifold must be equipped with a drain valve, a supply valve, a purge valve, and the
appropriate number of stage valves as minimum. All components for extending the standard version to
a stage control system are available as options (see table below) or must be supplied by the customer.
Options
On/Off control
Stage control
Fibre Media
Composite non particle-releasing glass fibre media with anti-microbial im-
pregnation and A2, S2, d0 (UL Class 1) fire rating.
Available in 75% (100mm), 85% (150mm) and 95% (200mm) efficiencies.
●
●
Polyester Media
Robust patented synthetic media with hygroscopic impregnation and DIN
EN53483 Class F1 fire rating.
Available in 85% (200mm), 95% (300mm) efficiencies.
●
●
Droplet Separator
Droplet Catching matrix increasing maximum face velocity limit without drop-
let carry-over from 3.5 m/s (689 fpm) to 4.5 m/s (886 fpm).
●
●
Evaporative module Blanking
Kit to secure Nortec ME and prevent air-bypass within the duct / AHU.
●
●
Leak Detection
Provides additional fault indication for the Nortec ME by monitoring for stand-
ing water detected in duct / AHU.
●
●
Stage valves
Valve kit which facilitates stage control of direct feed systems using customer
controls or the ME Direct Feed Stage Control Unit.
Available in 2, 3, 4 and 5 stage versions.
–––
●
Inlet, drain and purge valve
Valve kit for customers who wish to create their own basic on/off direct feed
control system.
●
●
On/Off control unit
On/Off control unit for simple control of direct feed systems which includes
timed purge function to enhance system hygiene.
●
–––
Stage control unit
Stage control unit for simple analogue control of direct feed systems which
includes timed purge function to enhance system hygiene.
–––
●