Se steam line – Nortec SAM-e User Manual
Page 40
37 | SAM-e Installation
SE Steam Line
Table 3: SE Steam-Line
Unit
No. of
Steam
Outlets
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss
per foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
SE 050
1
50
1-1/2”
1-3/4”
0.11
37 ft
SE 100
1
100
1-1/2”
1-3/4”
0.11
90 ft
SE 175
1
175
3”
3”
0.16
90 ft
SE 250
1
250
3”
3”
0.16
180 ft
SE 375
1
375
4”
4”
0.22
180 ft
SE 575
1
575
4”
4”
0.22
220 ft
SE 750
2
750
2 x 4”
2 x 4”
0.44
260 ft
SE 1050
2
1050
2 x 4”
2 x 4”
0.44
260 ft
• Based on 3” duct static pressure.
• Maximum duct static pressure for SE is 12” w.c.
See also other documents in the category Nortec Equipment:
- HumDigital (28 pages)
- NHDI Nortec OnLine (16 pages)
- SynPur (37 pages)
- Steam Distribution (15 pages)
- DRAABE Pure Water System (59 pages)
- AIRFOG Series (48 pages)
- NHDI Resistive Element (40 pages)
- LiveSteam v.1 (38 pages)
- OnLine NHRS (24 pages)
- HP Series (76 pages)
- LINKS 2 SETC (50 pages)
- Outdoor Temperature Sensor (2 pages)
- Off Digital Wall Humidistat (4 pages)
- LINKS 2 SC (44 pages)
- Off Digital Duct Humidistat (4 pages)
- BLOWER PACK For RH Series (6 pages)
- Outdoor Mount Temperature Sensor (2 pages)
- SETC Outdoor (32 pages)
- Off Digital Wall & Duct Humidistat (6 pages)
- 2-10 V Wall & Duct Humidity Sensor (6 pages)
- Steam Distributors (16 pages)
- SE Series (100 pages)
- MES2 (54 pages)
- LINKS XPS SETC (68 pages)
- LINKS 2 GSTC B+ (23 pages)
- Modbus (52 pages)
- RH2+ (62 pages)
- Blower Packs (31 pages)
- LONWORKS (36 pages)
- Remote Interface (34 pages)
- NH-EL Series (99 pages)
- ME Direct Feed (40 pages)
- ME Control (76 pages)
- MLP RO pump station (12 pages)
- ME Control Installation (48 pages)
- Air Humidification System BS (30 pages)
- ME Direct Feed Installation (48 pages)