Mini sam-e with pressurized steam, Mini sam-e pressurized with external separator – Nortec SAM-e User Manual
Page 29
SAM-e Installation | 26
Mini SAM-e with Pressurized Steam
Mini SAM-e Pressurized with External Separator
• Steam components in grey provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.
When pressurized steam enters SAM-e, pressure drops down to almost atmospheric pressure.
Therefore, it must be drained atmospherically, and the use of a condensate pump (rated for 212ºF)
must be used to raise condensate to a higher elevation.
Strainer
Manual Shut-Off
Valve (By Others)
Steam Main
F & T Steam Trap
Separator
Actuator & Valve
Pressurized condensate
return main
1” Air Gap
Drain
Steam from top of main
Manual Shut-Off
Valve (By Others)
6” min.
6” min
Return to non-pressurized
condensate return main
Duct Width
Duct
Height
Duct Floor
Mounting
bracket