Repair - troubleshooting – MovinCool 24HFU Service Manual User Manual
Page 27

MOVINCOOL 24HFU / 24HFU-1 SERVICE
PAGE 27
REPAIR - TROUBLESHOOTING
TROUBLE
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit does
Unit does
1) Defective control switch
Refer to 4-2
not operate
not operate
2) Defective auxiliary relay
Refer to 4-1
3) Defective drain switch
Refer to 4-5
Unit starts,
1) Defective overload relay
Refer to Wiring Diagram
but stops
2) Defective fan motor
Refer to 4-6
immediately
3) Defective compressor motor
Refer to 4-7
Unit operates,
1) Defective compressor motor
Refer to 4-7
but stops after
2) Defective overload relay
Refer to Wiring Diagram
a few minutes
3) Defective high pressure switch
Refer to 4-10
Water leakage
1) Defective drain pan (crack or hole)
Repair
from the unit
2) Defective drain hose
Repair or replace
(clogged or loose connection)
Before troubleshooting this system, the following inspection should be performed.
1-1.
Inspection of Power Source Voltage
Check the voltage of the power source.
24HFU & 24HFU-1: Single phase 230 volts (60Hz)
Check the operation and condition of the fuse or circuit breaker in the power source.
1-2.
Inspection of Air Filters
Remove the air filters and check the element. If it is dirty, wash it as described in the OPERATION
MANUAL supplied with the unit.
1-3.
Inspection of Drain Tank
Be sure tank is fully drained.
The following chart is provided as a guide for categorized problem remedies. Detailed information is
contained in the OPERATION MANUAL supplied with the unit.
Abnormal
1) Loose compressor mounting nut
Tighten
noise and
2) Deformed or worn rubber grommet
Replace
shaking
on the compressor mounting bolt
3) Interference with other materials.
Remove it
4) Interference of fan and scroll
Readjust
Insufficient
1) Clogged spine fin and/or air filter
Refer to 2-1 and/or
velocity of
wash the air filter
cooled air
2) Defective fan motor
Refer to 4-6
3) Defective fan motor capacitor
Refer to 4-3
Insufficient
Compressor and
1) Abnormal environment condition
Refer to 2-2
cooling
fan motor rotate
2) Clogged spine fin
Refer to 2-1
properly
3) Leak in system
Refer to 5-1
4) Clogged refrigerant system
Refer to 5-1
Compressor motor 1) Defective compressor motor
Refer to 4-7
does not rotate
2) Defective compressor capacitor
Refer to 4-3
3) Defective auxiliary relay
Refer to 4-1
4) Defective control switch
Refer to 4-2
5) Defective overload relay
Refer to Wiring Diagram
6) Defective wiring connection
Check and correct
7) Defective thermostat
Refer to 4-9
8) Defective compressor relay
Refer to 4-11
Cooled air
Blower motor does 1) Defective fan motor
Refer to 4-6
does not
not rotate
2) Defective fan motor capacitor
Refer to 4-3
come out
3) Defective wiring connection
Refer to 4-8
4) Defective auxiliary relay
Refer to 4-1
■ TroubleShooting Chart