beautypg.com

Dometic BRISK AIR 590 SERIES User Manual

Page 9

background image

9

INSTALLATION INSTRUCTIONS

TROL KIT

A. If your installation included the optional electric heat kit,

install it at this time. Follow the instructions with the

heat package for its installation procedure.

B. Terminate the 4-conductor control cable(s) protruding

into the 4-/4” x 4-/4” (±/8”) roof opening. The

cable(s) must be terminated with an RJ--4C-6P telephone

connector. Refer to the crimp tool manufacture for

crimping instructions.

Important:

RJ-11-4C-6P connectors must be installed as shown

in FIg. 4A.

C. Remove the junction box cover from the Electronic

Control Kit. See FIG. .

D. Plug the electrical conduit (6-pin connector) from the

upper unit into the mating connector in Electronic Con-

trol Kit. See FIG. .

E. Plug the control cable(s) into the telephone jack(s) on

the Electronic Control Kit. (It does not matter which

one.)

F. Route the Remote Temperature Sensor cable, if appli-

cable, through the same round grommet where freeze

control wires go into the Electronic Box. See FIG. .

Connect it to the connector that matches its color.

g. Insert the Freeze Control Sensor approximately ” into

the evaporator coil fins as shown in FIG. 12.

H. Locate the electronic control kit on the ceiling template

as shown in FIG. 3. Drive two (2) #0 x 3/8” blunt point

phillips head screws (provided) through ceiling template

into holes in electronic control kit to hold it in place.

8. WIRINg OF SySTEM

A. CONNECTION OF LOW VOLTAgE WIRES

Disconnect the positive (+) 12 volt DC terminal at the

supply battery. Damage to equipment could occur if

the 12 volt DC is not shut off.

. Connect the previously run 2 VDC to the red and

black wires protruding from the Electronic Control Kit.

(In multiple zone installations, this needs to be done

at only one zone.) Connect +2 VDC to the red wire;

-2 VDC to the black wire.

2. Connect the previously run furnace thermostat wires

(if applicable) to the blue wires protruding from the

electronic Control Kit. The polarity of these connec-

tions does not matter. If not used, terminate wire with

twist connector.

3. Connect the previously run Energy Management

System wires (if applicable) to the yellow wires

protruding from the Electronic Control Kit. The

polarity of these connections does not matter. If not

used, terminate wire with twist connector.

FIg. 11

FIg. 12

FIg. 13

This manual is related to the following products: