Troubleshooting, Specifications, Limited warranty – Infloor Thermostat 29050 V2 User Manual
Page 4

Troubleshooting
Problem
Solution
Thermostat works but no
heat from the system.
1. Check wiring connections.
2. If GFCI is tripped, reset thermostat
with on/off switch.
3. Check resistances on floor heating
system. See manual for system.
No display
1. Check wiring connections.
2. Check circuit breaker or other
protection “upstream” of
thermostat.
GFCI is tripped
1. Check wiring connections.
2. Reset thermostat by switching
on/off.
3. Check resistances on floor heating
system. See manual for system.
Heating occurs at the wrong
times
1. Check that the current time and
schedule times are properly set to
AM or PM.
2. On uninsulated concrete
SmartStart may start heating very
early. You may turn this feature off
if not desired.
Err1:Wrong floor sensor
Floor sensor not correct type or
out of range. Check floor sensor
resistance.
Err2:Floor sensor shorted
Floor sensor short-circuited. Turn off
power at breaker. Make sure wires
are not crossed at the terminals.
Or replace sensor. Or Reset Factory
Defaults.
Err3:Floor sensor missing
Floor sensor not attached and
thermostat is in floor sense mode.
Turn off power at breaker and attach
sensor. Or Reset Factory Defaults.
Err4/Err5:Internal sensor
fail
Internal air sensor is faulty. Replace
thermostat or operate in floor sense
mode.
Err6:Internal temp limit
Internal temperature overlimit. Make
sure sunlight is not directed at the
thermostat or other heat sources in
proximity. Make sure load does not
exceed 15 amps. Otherwise, turn
off power at breaker and contact
factory.
Err7:End-of-life
“End-of-life” indication. GFCI will no
longer function correctly or safely.
Reset the circuit breaker or replace
thermostat.
Specifications
Power Supply
120/240 VAC, 50/60 Hz
Maximum Load
15 amps, resistive
Maximum Power
1800 watts at 120 VAC
3600 watts at 240 VAC
GFCI
Class A (5 milliamp trip nominal)
Display Range
32°F to 99°F (0°C to 37°C)
Setting Range
40°F to 99°F (4°C to 37°C)
Accuracy
± 0.9°F (0.5°C)
Environment
Indoor dry location only
Storage Temperature 0°F to 120°F (-17°C to 49°C)
Floor Sensor
Thermistor, 10k NTC type, double-insulated
Memory
Programming retained indefinitely
Current time/day will need reset if power is lost more than 30 minutes.
ETL Listing
Control No. 3037530
Conforms to UL 873, UL 943, CSA C22.2 No. 24, CSA/CAN C22.2 No. 144
Limited Warranty
Infloor warrants this control (the product) to be free from defect in material
and workmanship for a period of (3) years from the date of original purchase
from authorized dealers. During this period, Infloor will replace the product or
refund the original cost of the product at Infloor’s option, without charge, if
the product is proven defective in normal use. Please return the control to your
distributor to begin the warranty process.
This limited warranty does not cover shipping costs. Nor does it cover a product
subjected to misuse or accidental damage. This warranty does not cover the cost
of installation, diagnosis, removal or reinstallation, or any material costs or loss
of use.
This limited warranty is in lieu of all other warranties, obligations, or liabilities
expressed or implied by the company. In no event shall Infloor be liable for
consequential or incidental damages resulting from installation of this product.
Some states or provinces do not allow limitations on how long an implied
warranty lasts, or the exclusion or limitation of incidental or consequential
damages, so the above exclusions or limitations may not apply to you. This
warranty gives you specific legal rights and you may also have other rights that
vary from state to state.
Infloor Sales and Service
503 Gregg Dr.
Buena Vista, CO 81211
800.608.0562
719.395.3555 FAX
www.infloor.com