beautypg.com

Snowmelt install-2.ai – Infloor Snow Melt Heavy-Duty Cable User Manual

Page 2

background image

TESTING PROCEDURES FOR TXLP SNOW AND ICE MELTING CABLE

Cable Despription: 2 Black (non-heated power leads),

2 Green (ground wires) Spliced to the end of the blue heating cable.

1)

Verify the cable you ordered is the one that you received. Refer to the UL flag tag that is

attached to one of the black non-heated lead wires. This tag will list the following information:

Watts, Volts, Cable Length, Cable Spacing, Ohms and Amps.

2)

Visually check the cable for obvious flaws or breaks.

3)

With a digital ohm meter, check your resistance between the two block wires. Reading

should be between +/- 10% of the value listed on the UL tag. Record your readings for

warranty registration purposes.

4)

Again, using your digital ohm meter check the resistance between the black and the

green wires, the reading should be 1999, all blanks or infinity.

5)

Make sure all the blue heating cable and the splice are completely embedded in the

underlayment. Only the black and green lead wires are permitted to be out of the pour.

6)

During the installation of the topping, monitor the cable for any sudden changes in the

ohms.

7)

After the cable is installed, repeat steps 4 & 5.

8)

When performing an actual amperage test, never run the cable for more than 15 seconds.

9)

It’s very important to take a photo of the cable layout prior to the pour to avoid any

damage to the cable in the future.

GENERAL INFORMATION

TERMINAL INSULATION: Terminal insulation, if chosen or required, can be of a mineral wood or expanded polystrene. The

thickness depends on the local conditions, but normally 1-2 inches or R-12. When the heating cables are to be laid on top of

the insulation, cover the insulation with a wire mesh in order to prevent the cables from being pressed down into the insul-

ation during intallation.

VAPOR BARRIER: If a vapor barrier is required, it shall be of of non-metallic material such as plastic film. It must be located

so that no damage can occur due to mechanical causes or by overheating from the cables.

MECHANICAL INTERGRITY: When installing insulation and/or vapor barriers, it is important to make sure that the mech-

anical integrity of the pour is not compromised in anyway.

LAYOUT RESTRICTION: Heating cables must be installed in open areas only. The layout requires that the entire heating cable

be looped at even center spacing over the area that is to be heated. Both ends are terminated at a point where the power

connection is made. Details of cable length, on center spacing, loading, etc. are give on UL Tag. (MINIMUM DISTANCE BETWEEN

DISTANCE BETWEEN ADJACENT RUNS AND MININUM BENDING DIAMETER IS 2 INCHES).

When installing, it is important to remember that all of the heating cables, including splices to cold leads, must be embedded so

that only the non-heating leads are exposed outside the pour. By NEC standards a conduit is used to bring the leads out of the

pour. Minimum distance between the heating portion of the cable and any combustible surface shall be 1/32 inch. The heating

portion of the cable shall not touch, crossover, or overlap itself. As an option, measure and mark the center spacing within the

design area as a reference for cable layout. Lay the heating cable out starting and ending in the same location. The cable must be

laid at the calculated spacing. A template can be cut 1/4” less than the required center spacing. This will help insure the proper

layout of the heating cable. Cables should be secured using approved means (See Page 4) as noted within these instructions.

The cables should not be left unprotected for long periods of time or damage may occur. Concentrationof heating cables around

columns, drains, etc., may lead to overheating.

OUTDOOR COVERING MATERIALS: Asphalt, concrete or pavers (in sand or concrete) can be used as covering materials. The

coverings and bonding materials must be able to withstand a continuous temperature of 122 degress F (50 degrees C).

TEMPERATURE CONDITIONS: Heating cables should not be laid in temperatures below 25 F as the outer plastic jacket becomes

brittle at low temperatures and may crack as a result of an impact or jolt.