VENTING INSTALLATION
INSTRUCTIONS

Continued

HIGH ALTITUDE INSTALLATION

Your DESA direct-vent fireplace has been tested and approved for
elevations from 0-2000 feet (USA) and elevations from 0-4500 feet
(Canada) .
When installing this fireplace at an elevation above 2000 feet (in the
USA), you may need to decrease the input rating by changing the
existing burner orifice to a smaller size. Reduce input 4% for each
1000 feet above sea level. Check with your local gas company for
proper orifice size identification.
When installing this fireplace at an elevation above 4500 feet (in
Canada), check with local authorities.
Consult your local gas company to help determine the proper orifice
for your location.
For assistance with any high altitude installation contact DESA’s
Customer Service Department at 1-866-672-6040.

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination (Cont.)

High Altitude Installation

Parts Lists for Venting Kits and Components

Vertical Venting

V = 40' max.

Figure 24 - Vertical Venting Configuration With No Horizontal
Run (Vertical Round High Wind Termination Shown)

Note: Install restrictor
into inner collar of
fireplace as shown.

45° Elbow

PARTS LISTS FOR VENTING KITS AND
COMPONENTS

DESA (5/8") Pipe & Vent Kits

Number Description

P58-6

6" Section Double Wall Pipe, Galvanized

P58-12

12" Section Double Wall Pipe, Galvanized

P58-24

24" Section Double Wall Pipe, Galvanized

P58-36

36" Section Double Wall Pipe, Galvanized

P58-48

48" Section Double Wall Pipe, Galvanized

PA58-712 Adjustable 7"-12" Section Double Wall Pipe, Galva-

nized

FPA58-6 6" Duravent Collar to FMI Pipe Adaptor (6" Collar/Pipe

Section)

DPA58-6 6" FMI Collar to Pipe Duravent Adaptor (6" Collar/Pipe

Section)

E58-45

45 deg. Elbow, Galvanized

E58-90

90 deg. Elbow, Galvanized

FSE58-45 45 deg. Starter Elbow, Galvanized (Duravent Collar to

FMI Pipe)

DSE58-45 45 deg. Starter Elbow, Galvanized (FMI Collar to

Duravent Pipe)

VKG-58

Ground Floor Vent Kit

VKB-58

Basement Vent Kit

VKS-58

Snorkel Vent Kit

VKR-58

Roof Vent Kit

VKC-58

Corner Vent Kit

HTK

Horizontal Round Termination Kit

HT-58

Horizontal Round Termination, Galvanized

HTKS-47 Horizontal Square Termination Kit

Includes: Square Termination, Wall Firestop, and 45° Elbow

HTS-58

Horizontal Square Termination, Galvanized

VT-58

Vertical Round Termination, Galvanized

ST-58-14 14" Snorkel Termination, Galvanized
ST-58-36 36" Snorkel Termination, Galvanized
SC-58

Storm Collar, Galvanized

WF-58

Wall Firestop, Galvanized

RF-58-6

Roof Flashing - 0 to 6/12 Pitch, Galvanized